6
Parameter Settings and Functions
76
© Copyright Reserved Autonics Co., Ltd.
6.4.11
Alarm Output Off
Available only if alarm output option is set to alarm latch or alarm latch and standby
sequence1, alarm latch and standby sequence2. It can be set to turn off alarm output
when alarm output is on, alarm output conditions have been removed, or an alarm
output off signal that is greater than the minimal signal band is received. (However,
alarm output off is unavailable when alarm conditions remain in effect.)
You can assign the digital input terminals (DI-1, DI-2) for the alarm output off feature.
For more information about digital terminal (DI) setting, please
refer to '6-6-4-1'.
After deactivating the alarm output, it will function normally for
the next alarm output occurrence.