6
Parameter Settings and Functions
© Copyright Reserved Autonics Co., Ltd.
67
6.4.1
Alarm Output Target Channel Settings
Users can set channels in which alarm output (2EA or 4EA) will be activated.
Group
Parameter
Range
Factory Default
Unit
Alarm Setting
Group
Alarm Target
Ch
CH1, CH2, CH1 and
CH2, CH1 or CH2
Alarm 1, 3 : CH1
Alarm 2, 4 : CH2
-
In case of heating/cooling control, Alarm 1 and Alarm 2 are used as a
cooling control output; therefore, they cannot be used as an alarm
output.
6.4.2
Alarm Output Operating Mode Settings
Select the desired alarm output mode.
Mode
Alarm Output
Description (Factory Default)
OFF
Alarm off
AL-1
Deviation High-limit Alarm ( +FS)
If PV/SV deviation occurs higher than set
value of deviation temperature, alarm output
will be ON.
High limit deviation temperature can be set in
AL1.H/AL2.H/AL3.H/AL4.H.
AL-2
Deviation Low-limit Alarm ( +FS)
If PV/SV deviation occurs lower than set value
of deviation temperature, alarm output will be
ON.
Low-limit deviation can be set in
AL1.H/AL2.H/AL3.H/AL4.H.
AL-3
Deviation High/Low-limit Alarm ( +FS)
If PV/SV deviation occurs higher than high-
limit deviation or lower than low-limit
deviation, alarm output will be ON.
High-limit deviation can be set in
AL1.H/AL2.H/AL3.H/AL4.H.
Low-limit deviation can be set in
AL1.H/AL2.H/AL3.H/AL4.H.
AL-4
Deviation High/Low-limit Reverse Alarm
If PV/SV deviation occurs higher than low-limit
deviation or lower than high-limit deviation,
alarm output will be ON High-limit deviation
can be set in AL1.H/AL2.H/AL3.H/AL4.H.
Low-limit deviation can be set in
AL1.H/AL2.H/AL3.H/AL4.H.
AL-5
Absolute Value High-limit Alarm
If PV is higher than the absolute value of
temperature, alarm output will be ON.
Alarm absolute value can be set in
AL1.H/AL2.H/AL3.H/AL4.H.
Summary of Contents for TM Series
Page 1: ...User Manual ...
Page 2: ......
Page 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Page 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Page 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Page 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Page 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Page 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Page 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Page 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Page 96: ......
Page 97: ......