6.2.1.3
Heating and Cooling Control
Heating and cooling control mode: heating and cooling with a single temperature
controller when it is difficult to control subject temperature with only heating or cooling.
Heating and cooling control mode controls the object using different PID time
constants for each heating and cooling. It is also possible to set heating and cooling
control in both PID control or ON/OFF control mode. Heating/cooling output can be
selected among Relay output, SSR drive voltage output and current output depending
on model types choosen according to your application environment. (Note that only
standard SSR control is available for SSR drive output in OUT2.)
For heating/cooling control, each output for heating and cooling is automatically
allocated as described in the following table.
Heating
Control
Cooling
Control
Remarks
TM4 Series
CH1 OUT
CH2 OUT
Heating output: Control output selection
by model is available.
Cooling output: Control output selection
by model is available.
CH3 OUT
CH4 OUT
TM2 Series
CH1 OUT
AL1 OUT
Heating output: Control output selection
by model is available.
Cooling output: Relay output fixed
CH2 OUT
AL2 OUT
For TM2 Series, heating output can be selected by models from
relay output, SSR output and current output. Cooling output is fixed
to relay output.
Summary of Contents for TM Series
Page 1: ...User Manual ...
Page 2: ......
Page 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Page 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Page 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Page 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Page 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Page 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Page 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Page 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Page 96: ......
Page 97: ......