Do-more H2 Series PLC User Manual, 1st Edition, Rev. F - H2-DM-M
7–15
Chapter 7: Specifications - Specialty Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
H2-ECOM100 LED Indicators
H2-ECOM100 Network Identifiers
Each module must be assigned at least one unique identifier to make it possible for other devices
to recognize it on the network. There are four identifiers possible with the ECOM modules:
• Module ID
• Name
• IP (Internet Protocol) Address
• Ethernet (MAC) Address
The first three are user selectable but the MAC address is set at the factory. The type of identifier
chosen depends on the requirements of your particular application. PC-to-PLC communication
typically uses one type of identifier while PLC-to-PLC communication may require another. The
following table summarizes Network Identifiers and their uses:
H2-ECOM100 LED Descriptions
Indicator
Status
Description
STATUS
ON (Green)
Module is powered up and functional
OFF
Module powerup failed
LINKGD
ON (Green)
Properly connected to network
OFF
Not connected to network or incorrect configuration
ACTIVE
ON or FLASHING (Red)
Active Network Data
OFF
Network Idle
ERROR
ON or FLASHING (Red)
A fatal error has occurred
OFF
No error present
100MBIT
ON
100Base T Frequency detected
OFF
(With ACTIVE LED ON) - 10Base T Frequency detected
STATUS
LINKGD
ACTIVE
ERROR
100MBIT
H2-ECOM100
10/100 BASE-T
ETHERNET PORT
10/100 BASE
10/100 BASE
0/ 00
S -TT
-
ETHERNET PORT
ETHERNET PORT
HERNET PORT
Network Identifiers
Identifier
How to Set
Format
Communication
Notes
Module ID
DIP Switch
Number 1–63
PLC-to-PLC or PC-to-PLC
Disables Module ID in NetEdit3
NetEdit3
Number 1–90
PLC-to-PLC or PC-to-PLC
DIP Switch must be set to “0”
NetEdit3
Number 1–999,999,999
PC-to-PLC only
>90 (Not for PLC-to-PLC)
Name
NetEdit3
32 Alphanumeric Characters
PC-to-PLC only
HMI software may have restrictions
IP Address
NetEdit3
4 sets of numbers, up to three
digits each (192.168.76.3)
PC-to-PLC, (PLC-to-PLC
Client/Server using TCP/IP or
Modbus TCP protocols)
See your Network Administrator for
IP addresses
Ethernet (MAC) Address
Set at Factory
12 Hex digits
PC-to-PLC only
Factory assigned for IPX