D2–08CDR, 4 pt. DC Input / 4pt. Relay Output
D2-08CDR 4-pt. DC In / 4pt. Relay Out
General Specifications
Base Power Required 5VDC
200mA
Terminal Type (included)
Removable; D2-8IOCON
Status Indicator
Logic side
Weight
3.5 oz. (100g)
Input Specifications
Inputs per Module
4 (sink/source)
Input Points Consumed
8 (only first 4-pts are used)
Commons per Module
1
Input Voltage Range
20–28 VDC
Peak Voltage
30VDC
ON Voltage Level
19VDC minimum
OFF Voltage Level
7VDC maximum
AC Frequency
N/A
Input Impedance
4.7 k
q
Input Current
5mA @ 24VDC
Maximum Current
8mA @ 30VDC
Minimum ON Current
4.5 mA
Maximum OFF Current
1.5 mA
OFF to ON Response
1 to 10 ms
ON to OFF Response
1 to 10 ms
Fuses (input circuits)
None
Output Specifications
Outputs per Module
4
Outputs Points Consumed
8 (only first 4-pts are used)
Commons per Module
1
Output Type
Relay, form A (SPST)
Operating Voltage
5–30 VDC; 5–240 VAC
Peak Voltage
30VDC; 264VAC
ON Voltage Drop
N/A
AC Frequency
47 to 63 Hz
Minimum Load Current
5mA @ 5VDC
Max Load Current (resistive)
1A/point ; 4A/module
Max Leakage Current
0.1 mA @ 264VAC
Max Inrush Current
3A for < 100 ms, 10A for < 10ms (common)
OFF to ON Response
12ms
ON to OFF Response
10ms
Fuses (output circuits)
1 (6.3 A slow blow, replaceable);
Order D2-FUSE-3 (5 per pack)
ZIPLink Module
ZL-RTB20 (Feedthrough)
ZIPLink Cable
ZL-D2-CBL10 (0.5 m)
ZL-D2-CBL10-1 (1.0 m)
ZL-D2-CBL10-2 (2.0 m)
0
1
2
3
4
Points
Out-
puts
1A / Pt.
Derating Chart
0
10
20
30
40
50 55
Ambient Temperature (°C/°F)
32
50
68
86
104 122131
C
°
F
°
Inputs
5mA /
Pt.
CA
O
0
1
2
3
1
2
3
CB
L
5--240 VAC
5--30 VDC
L
L
L
24VDC
+
--
Sink
Source
COM
OUTPUT
To LE D
Internal module circuitry
6.3A
5--240 VAC
L
5--30 VDC
Optical
COM
Isolator
INPUT
24VDC
V+
To LE D
Internal module circuitry
+
Sink
Source
1
2
3
CB
0
1
2
3
L
D2-08CDR
IN/
OUT
24VDC/
RELAY
0
1
2
3
A
CA
0
L
L
L
0
1
2
3
B
20-28VDC
8mA
5-240VAC
1A 50/60Hz
5-30VDC
5mA-1A
1
2
3
CB
0
1
2
3
L
D2-08CDR
IN/
OUT
24VDC/
RELAY
0
1
2
3
A
CA
0
L
L
L
0
1
2
3
B
20-28VDC
8mA
5-240VAC
1A 50/60Hz
5-30VDC
5mA-1A
Typical Relay Life (Operations)
Voltage/Load
Current
Closures
24VDC Resistive
1A
500k
24VDC Solenoid
100k
110VAC Resistive
500k
110VAC Solenoid
200k
220VAC Resistive
350k
220VAC Solenoid
100k