Do-more H2 Series PLC Hardware User Manual, 1st Edition, Rev. F - H2-DM-M
5–10
Chapter 5: Specifications - Discrete I/O Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
D2-08NA-2, AC Input
D2-08NA-2 AC Input
Inputs per Module
8
Commons per Module
1 (2 I/O terminal points)
Input Voltage Range
170–265 VAC
Peak Voltage
265VAC
ON Voltage Level
150VAC minimum
OFF Voltage Level
40VAC maximum
AC Frequency
47–63 Hz
Input Impedance
18k
q
@ 60 Hz
Input Current
9mA @ 220VAC, 50Hz
11mA @ 265VAC, 50Hz
10mA @ 220VAC, 60Hz
12mA @ 265VAC, 60Hz
Minimum ON Current
10mA
Maximum OFF Current
2mA
Base Power Required 5VDC
100mA
OFF to ON Response
5 to 30 ms
ON to OFF Response
10 to 50 ms
Terminal Type (included)
Removable; D2-8IOCON
Status Indicator
Logic side
Weight
2.5 oz. (70g)
ZIPLink Module
ZL-RTB20 (Feedthrough)
ZIPLink Cable
ZL-D2-CBL10 (0.5 m)
ZL-D2-CBL10-1 (1.0 m)
ZL-D2-CBL10-2 (2.0 m)
C
C
0
1
2
3
4
5
6
7
Internally
connected
220VAC
0
2
4
6
8
0
10
20
30
40
50 55
Ambient Temperature (°C/°F )
32
50
68
86
104
122131
C
°
F
°
Points
Derating Chart
Optical
COM
Isolator
INPUT
220VAC
V+
To LE D
Internal module circuitry
COM
C
4
5
6
7
0
1
2
3
187-238V
10-20mA
50/60Hz
C
D2-08NA-2
IN
220
V
0
1
2
3
4
5
6
7
C
4
5
6
7
0
1
2
3
187-238V
10-20mA
50/60Hz
C
D2-08NA-2
IN
220
V
0
1
2
3
4
5
6
7