background image

Do-more H2 Series PLC User Manual, 1st Edition, Rev. F - H2-DM-M

6–13

Chapter 6: Specifications - Analog I/O Modules

1
2
3
4
5
6
7
8
9

10
11
12
13
14

A

B

C

D

F2-08AD-1, Analog Input

F2-08AD-1 8-Channel Analog Current In

Number of Channels

8, single ended (1 common)

Input Ranges

4 to 20mA current

Resolution

12 bit (1 in 4096)

Low-pass Filtering

-3 dB at 200 Hz, (-6 dB per octave)

Input Impedance

250

q

 ±0.1%, 1/2W current input

Absolute Maximum 

Ratings

-45mA to +45mA

Converter Type

Successive approximation

Conversion Time 

(PLC Update Rate)

8 channels per scan maximum

Linearity Error           

(End to End)

±1 count (0.025% of full scale) 

maximum

Input Stability

±1 count

Full Scale Calibration 

Error (Offset error not 

included)

±5 counts max., @ 20mA current input

Offset Calibration Error

±2 counts max., @ 4mA current input

Step Response

1 ms to 95% of F.S. change

Maximum Inaccuracy

±0.1% @ 77ºF (25ºC)
±0.25% 32º to 140ºF (0º to 60ºC)

Accuracy vs Temperature

±50ppm/ºC maximum full scale 
(Including max. offset change of two 

counts)

Recommended Fuse

0.032 A, Series 217 fast-acting, current 

inputs

Base Power Required 

5VDC

100mA

External Power Supply

5mA maximum, +10 to +30VDC

Operating 

Temperature

32º to 140ºF (0º to 60ºC)

Storage Temperature

-4º to 158ºF (-20º to 70ºC)

Relative Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3-304

Terminal Type 

(included)

Removable; D2-8IOCON

ZIPLink Module

ZL-RTB20 (Feedthrough)

ZIPLink Cable

ZL-D2-CBL10 (0.5 m)

ZL-D2-CBL10-1 (1.0 m)

ZL-D2-CBL10-2 (2.0 m)

CH1

4--wire

4--20mA

Transmitter

Optional

OV

A to D

Converter

Internal

Module

Wiring

An
al

og
Sw
itch

+

--

E xternal

P/S

250

S ee NOTE 1

250

250

250

CH4

3--wire

4--20mA

Transmitter

CH6

2-wire

4--20mA

Transmitter

CH8

2-wire

4--20mA

Transmitter

+

--

+

--

+

--

+

--

--

+

+

0 VDC

+24 VDC

CH1+

CH3+

CH5+

CH7+

CH8+

CH6+

CH4+

CH2+

+

--

24VDC

DC
to

DC

Co
nv

er

te

r

+5V

+15V

0V

--15V

One count in the specification table is equal to one least significant 

bit of the analog data value (1 in 4096).
Note 1: Shields should be grounded at the signal source.

More than one external power supply can be used provided all the power supply commons are connected. A Series 217, 0.032A, fast-acting 

fuse is recommended for 4-20 mA current loops. If the power supply common of an external power supply is not connected to 0 VDC on the 

module, then the output of the external transmitter must be isolated. To avoid “ground loop” errors, recommended 4-20 mA transmitter types 

are: 2 or 3 wire - Isolation between input signal and power supply or 4 wire - Isolation between input signal, power supply, and 4-20 mA 

output

+24V

CH2+

CH4+

CH6+

CH8+

0V

CH1+

CH3+

CH5+

CH7+

F2-08AD-1

IN

ANALOG

8CH

10-30VDC

  5mA

ANALOG IN

  4-20mA

+24V

CH2+

CH4+

CH6+

CH8+

0V

CH1+

CH3+

CH5+

CH7+

F2-08AD-1

IN

ANALOG

A

8CH

10-30VDC

  5mA

ANALOG IN

 4-20mA

Summary of Contents for Do-more H2 PLC Series

Page 1: ...er Manual Manual Number H2 DM M H2 DM1E D2 08ND3 IN 12 24 VDC 0 1 2 3 4 5 6 7 D2 08ND3 IN 12 24 VDC 0 1 2 3 4 5 6 7 OUT A B F2 16TD1P 12 24 VDC 10 2 26 4 VDC 0 25A CLASS2 A 0 1 2 3 24V 0 1 2 3 B 0V 4...

Page 2: ...Notes...

Page 3: ...in hazardous environments requiring fail safe performance such as in the operation of nuclear facilities aircraft navigation or communication systems air traffic control direct life support machines o...

Page 4: ...vida o sistemas de armamentos en las cuales la falla del producto puede resultar directamente en muerte heridas personales o da os f sicos o ambientales severos Actividades de Alto Riesgo Automationdi...

Page 5: ...n cessitant une s curit absolue par exemple l exploitation d installations nucl aires les syst mes de navigation a rienne ou de communication le contr le de la circulation a rienne les quipements de s...

Page 6: ...Notes...

Page 7: ...ory Issue Date Description of Changes 1st Edition 9 12 Original Revision A 9 12 Minor corrections made throughout manual Revision B 02 13 Added H2 ERM100 module data Minor corrections made throughout...

Page 8: ...Notes...

Page 9: ...ore Designer Software System Requirements 1 5 Step 1 Install Do more Designer Software 1 6 Step 2 Launch Do more Designer Software 1 9 Step 3 Install Hardware 1 11 Step 4 Apply Power to the Do more PL...

Page 10: ...cations 3 4 Port 1 Specifications USB 3 4 Port 2 Specifications Serial 3 4 USB Type B Slave Input Specifications 3 4 Port 3 Specifications Ethernet 3 5 Ethernet Specifications 3 5 Ethernet Expansion I...

Page 11: ...put 5 10 D2 16NA AC Input 5 11 D2 04TD1 DC Output 5 12 D2 08TD1 DC Output 5 13 D2 08TD2 DC Output 5 14 D2 16TD1 2 DC Output 5 15 D2 16TD2 2 DC Output 5 16 F2 16TD1P DC Output With Fault Protection 5 1...

Page 12: ...dule Jumpers 6 11 F2 04AD 2 L Addressing 6 12 F2 08AD 1 Analog Input 6 13 Setting the Module Jumpers 6 14 F2 08AD 1 Addressing 6 15 F2 08AD 2 Analog Input 6 16 Setting the Module Jumpers 6 17 F2 08AD...

Page 13: ...Version 1 1 or Newer 6 59 Input Resolution Selection WYn 4 6 60 Input and Output Range Selection WYn 5 6 61 Input Track and Hold Selection WYn 6 6 62 Chapter 7 Specifications Specialty Modules Special...

Page 14: ...100 LED Indicators 7 23 H2 EBC100 Overview 7 23 H2 EBC100 Specifications 7 23 H2 EBC100 LED Indicators 7 24 H2 ERM 100 H2 EBC100 Network Identifiers 7 24 H2 ERM 100 H2 EBC100 Network Layouts 7 27 H2...

Page 15: ...I O Modules Position and Wiring 8 13 Slot Numbering 8 13 Module Placement Restrictions 8 13 Wiring the Different Module Connectors 8 14 I O Wiring Checklist 8 15 ZIPLink Wiring System 8 16 I O Wiring...

Page 16: ...C Hardware User Manual 1st Edition Rev F H2 DM M viii Appendix A Do more Product Weight Table Do more Product Weight Table A 2 Appendix B European Union Directives CE European Union EU Directives B 2...

Page 17: ...1 5 Do more Designer Software System Requirements 1 5 Step 1 Install Do more Designer Software 1 6 Step 2 Launch Do more Designer Software 1 9 Step 3 Install Hardware 1 11 Step 4 Apply Power to the D...

Page 18: ...applying power to the PLC establishing a communications link and creating saving and writing a project to the CPU Once these steps are completed your Do more PLC will be running a ladder logic project...

Page 19: ...n in the left hand margin the paragraph to its immediate right will be a warning This information could prevent injury loss of property or even death in extreme cases Any warning in this manual should...

Page 20: ...n also use an Ethernet or Serial D2 DSCBL cable for programming but we recommend using a USB cable just plug it in and it works USB A to USB B Programming Cable PC Running Windows XP Vista Windows 7 W...

Page 21: ...put and output signal ranges including bipolar Several specialty modules are also available Do more Designer Software System Requirements The Do more Designer Windows based programming software works...

Page 22: ...lready installed this screen will detail the version number of the software being replaced and the one being installed click Next to continue An alert window will appear requesting that all anti virus...

Page 23: ...to install whereas Complete installation installs all of the program features available The Complete installation is selected by default and is recommended for first time users Select the installation...

Page 24: ...tware on your PC s desktop Click Yes or No to continue with the installation The software will now install the needed files and folders with the Setup Status window detailing the status of the install...

Page 25: ...PC s Start menu or All Programs menu If the software link is not embedded in the Start menu use the path Start All Programs Do more Designer x x Do more Designer x x to launch the software The Do mor...

Page 26: ...on to store the project or use the default location Click OK after your selections have been made to continue The Main programming window and Instruction Palette shown below will open The Instruction...

Page 27: ...ps to firmly secure the module to the base WARNING Minimize the risk of electrical shock personal injury or equipment damage Always disconnect the system power before installing or removing any system...

Page 28: ...WG is the recommended size Do not over tighten the connector screws the recommended torque value is 7 81 lb in 0 882 N m NOTE You can connect either a 115VAC or 220VAC supply to the AC terminals Once...

Page 29: ...ications link To open the Link Wizard select the New Link button in the Links section of the Main Page s Launchpad as shown below The Link Wizard will first ask you to choose which communications port...

Page 30: ...configure each link by selecting the Link Editor button from the lower left corner of the Link Wizard The Configure Link dialog will open as seen below allowing you to select PLC types port parameters...

Page 31: ...isable enable or delete links Choose the appropriate link select OK and the software will connect to the Do more PLC If the mode selector switch on the CPU module is not in the Term position when conn...

Page 32: ...isplays may show incorrect information If the memory configuration in the disk based project contains elements that are incompatible with the memory configuration currently in the Do more PLC the mess...

Page 33: ...mparison are red which notes items that exist only in the project on the PC and not in the PLC and black which highlights items that are identical in both projects There are also numerous checkbox and...

Page 34: ...ive Notice the status bar indications which show PLC type memory usage communication status PLC errors PLC mode etc Hovering your mouse over the status bar will highlight the items that are selectable...

Page 35: ...onfiguration tab in the Project Browser or by clicking the XY Configure icon in the Project Toolbar On the left side of the System Configuration window is an index of topics titled Configuration Entri...

Page 36: ...led and they must match for the PLC to work properly NOTE If the manually configured I O modules do not match the installed I O modules the PLC will not go into Run Mode After you have set the configu...

Page 37: ...configuration will allow you to place that module in an Optional state This will allow the PLC to function properly without any hardware mismatch errors As previously mentioned the Do more PLC will n...

Page 38: ...s index This option will display the assigned addresses for the configured modules as seen below These X Y WX and WY addresses are automatically assigned by Do more Designer You have the option to man...

Page 39: ...blue Now you are ready to begin entering the example ladder logic below Rung 1 Place the box cursor in the NOP position on Rung 1 If the Instruction Palette is not open then click Instructions from t...

Page 40: ...l be T1 Done This feature works for all structures including timers counters PID loops and strings Many system data types such as Main and FirstScan as well as user created devices like ECOM CTRIO or...

Page 41: ...otice the shortcuts that are available for wire drawing The wire that should now appear in your ladder could have also been drawn using the shortcut Ctrl Down Arrow NOTE There are also Delete Wire opt...

Page 42: ...Lastly you will need to add an Out coil to the end of Rung 2 Place the cursor at the end of the rung and either select Out from the Ladder Palette Bar or just type OUT and select the Out instruction f...

Page 43: ...gin signifies logic that has not been accepted So once you have verified your logic click the Accept button in the Project Toolbar or the Ladder Palette Bar to accept the changes You should now see bl...

Page 44: ...utton is not active then you must first connect to the PLC to activate the online portion of the Project Toolbar see the Establish Communication section of this chapter If you have altered the System...

Page 45: ...er elements entered into the Data View window you now need to activate their status To do so click the All Status icon on the Project Toolbar or select Debug All Status On The All Status On option wil...

Page 46: ...1_Start s current value is OFF Click the ON button under the Edits column and the Write Current Edit and the Writes All Edits buttons will appear at the top of the window These buttons will write indi...

Page 47: ...free to experiment with a program of your own and don t forget that the software Help file is an essential tool to use when programming your controller Accessing the Help File TheDo more Designersoftw...

Page 48: ...Do more H2 Series PLC Hardware User Manual 1st Edition Rev F H2 DM M 1 32 Chapter 1 Getting Started 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D Notes...

Page 49: ...Do more H2 Series PLC Overview 2 2 2 Chapter Chapter Chapter In This Chapter Do more H2 Series PLC Overview 2 2 Do more DL205 System Compatibility 2 3 Communications 2 4...

Page 50: ...nstruction Set for ladder programs The new Do more Designer software with advanced programming and monitoring features will be used to create your new programs NOTE Because the Do more PLC supports a...

Page 51: ...F2 04RTD D2 04BDC1 1 F2 04THM D2 06BDC1 1 F2 02DA 1 L D2 09BDC1 1 F2 02DA 2 L D2 06BDC2 1 F2 02DAS 1 D2 09BDC2 1 F2 02DAS 2 Discrete I O Modules D2 08ND3 F2 08DA 1 D2 16ND3 2 F2 08DA 2 D2 32ND3 F2 4AD...

Page 52: ...Yes Yes Ethernet IP Yes Modbus RTU Client Master Yes Yes Modbus RTU Server Slave Yes Yes Modbus TCP Client Master Yes Yes Modbus TCP Server Slave Yes Yes DirectLOGIC RX WX Client Master Yes Yes Yes D...

Page 53: ...nications Ports Specifications 3 4 Port 1 Specifications USB 3 4 Port 2 Specifications Serial 3 4 USB Type B Slave Input Specifications 3 4 Port 3 Specifications Ethernet 3 5 Ethernet Specifications 3...

Page 54: ...RS 232 USB RS 232 Ethernet 10 100 Base T Program Memory Flash ROM Total I O points available X Y each configurable up to 65536 2048 default WX WY analog in out each configurable up to 65536 256 defaul...

Page 55: ...it default 512 X 512 Y 512 C 2048 V Immediate I O No Interrupt input hardware timed No Subroutines Program and Task code blocks up to memory limit Drum Timers Yes up to memory limit Table Instructions...

Page 56: ...ype B Slave Input Specifications Description Standard USB 2 0 Slave input for programming and online monitoring only with built in surge protection Not compatible with older full speed USB devices Cab...

Page 57: ...thernet IP Ethernet Expansion I O Master NOTE The above diagram illustrates the standard wire positions in the RJ45 connector It is recommended that all 10 100 Base T cables be Category 5 UTP cables E...

Page 58: ...I O GS EDRV100 GS Drives The Ethernet Expansion I O network uses Category 5 UTP cables for cable runs up to 100 meters 328ft with extended distances achieved through Ethernet switches WARNING It is hi...

Page 59: ...down menu select System Configuration Then from the System Configuration window select the CPU Configuration option under the Configuration Entries column Finally left click the Enable Ethernet I O M...

Page 60: ...ons The mode switch on the Do more CPU allows the user to externally select the different modes of operation There are three modes available RUN TERM and STOP Mode Switch Functions Mode Switch Positio...

Page 61: ...first powered up Changing the settings of the DIP switches requires that the base containing the controller be powered down and the controller removed from the base The DIP switches can then be chang...

Page 62: ...ot loader sequence that is they should be blinking in sequence from top to bottom then back to the top alternating between red and green Move the controller mode switch to RUN to the left Move the con...

Page 63: ...tween red and green Move the controller mode switch to RUN to the left Move the controller mode switch to TERM to the center Move the controller mode switch to RUN to the left Move the controller mode...

Page 64: ...Disk before performing this operation Power down the system containing the controller Remove the controller from the base Remove the battery from it s holder that is located on the back of the control...

Page 65: ...pter Chapter Chapter In This Chapter Base Unit Overview 4 2 Choosing a Base Type 4 2 AC Powered Base Units 4 3 24VDC Powered Base Units 4 4 125VDC Powered Base Units 4 5 Power Budget 4 6 Power Budget...

Page 66: ...more PLC offers 10 base configurations four chassis sizes with different power supply options The following diagram shows an example of a 6 slot base Your choice of base depends on three things Numbe...

Page 67: ...n 100 240 VAC Powered Bases Input Voltage Range 100 240 VAC 10 15 50 60 Hz Maximum Inrush Current 30A Maximum Power 80VA Voltage Withstand dielectric 1 minute 1500VAC between primary secondary and fie...

Page 68: ...28 8VDC D2 09BDC 1 12 24VDC 10 2 28 8VDC Specification 12 24 VDC Powered Bases Input Voltage Range 10 2 28 8 VDC with less than 10 ripple Maximum Inrush Current 10A Maximum Power 25W Voltage Withstan...

Page 69: ...Voltage Range 104 240 VDC 10 15 Maximum Inrush Current 20A Maximum Power 30W Voltage Withstand dielectric 1 minute 1500VAC between primary secondary and field ground Insulation Resistance 10M at 500VD...

Page 70: ...d and used by each device columns 3 and 4 Devices which fall into the Other category Row D are devices such as the C more Micro interface which also have power requirements but do not directly plug in...

Page 71: ...er Supplied Device 5V mA 24V Auxiliary Device 5V mA 24V Auxiliary Bases Bases D2 03B 1 2600 300 D2 04BDC1 1 2600 None D2 04B 1 2600 300 D2 06BDC1 1 2600 None D2 06B 1 2600 300 D2 09BDC1 1 2600 None D2...

Page 72: ...Do more H2 Series PLC Hardware User Manual 1st Edition Rev F H2 DM M 4 8 Chapter 4 Specifications Base Units 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D Notes...

Page 73: ...D2 32ND3 DC Input 5 7 D2 32ND3 2 DC Input 5 8 D2 08NA 1 AC Input 5 9 D2 08NA 2 AC Input 5 10 D2 16NA AC Input 5 11 D2 04TD1 DC Output 5 12 D2 08TD1 DC Output 5 13 D2 08TD2 DC Output 5 14 D2 16TD1 2 DC...

Page 74: ...Rev E H2 DM M 5 2 Table of Contents 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D D2 04TRS Relay Output 5 26 D2 08TR Relay Output 5 27 F2 08TR Relay Output 5 28 F2 08TRS Relay Output 5 29 D2 12TR Relay Ou...

Page 75: ...signifies an Input I O module a red bar signifies an Output I O module and a White bar signifies a combination Input Output module Module Type Blue Input Discrete Input Modules Part Number Number of...

Page 76: ...4 Isolated Relay Output 5 25 D2 08TR 8 Relay Output 5 26 F2 08TR 8 Relay Output 5 27 F2 08TRS 8 Isolated Relay Output 5 28 D2 12TR 12 Relay Output 5 29 Discrete Output Modules 0 1 2 3 C C C C L L L L...

Page 77: ...FF Current 1 5 mA Base Power Required 5VDC 50mA OFF to ON Response 1 to 8 ms ON to OFF Response 1 to 8 ms Terminal Type included Removable D2 8IOCON Status Indicator Logic side Weight 2 3 oz 65g ZIPLi...

Page 78: ...e Power Required 5VDC 100mA OFF to ON Response 3 to 9 ms ON to OFF Response 3 to 9 ms Terminal Type included Removable D2 16IOCON Status Indicator Logic side Weight 2 3 oz 65g ZIPLink Module ZL RTB20...

Page 79: ...dicator Module Activity LED Weight 2 1 oz 60g ZIPLink Module ZL RTB40 Feedthrough ZL LTB32 24 Sensor Input ZIPLink Cable ZL D24 CBL40 0 5 m ZL D24 CBL40 1 1 0 m ZL D24 CBL40 2 2 0 m ZL D24 CBL40 1P 1...

Page 80: ...Power Required 5VDC 25mA OFF to ON Response 3 to 9 ms ON to OFF Response 3 to 9 ms Terminal Type not included Removable 40 pin connector1 Status Indicator Module activity LED Weight 2 1 oz 60g ZIPLink...

Page 81: ...OFF Current 2mA Base Power Required 5VDC 50mA OFF to ON Response 5 to 30 ms ON to OFF Response 10 to 50 ms Terminal Type included Removable D2 8IOCON Status Indicator Logic side Weight 2 5 oz 70g ZIP...

Page 82: ...ON Current 10mA Maximum OFF Current 2mA Base Power Required 5VDC 100mA OFF to ON Response 5 to 30 ms ON to OFF Response 10 to 50 ms Terminal Type included Removable D2 8IOCON Status Indicator Logic s...

Page 83: ...rent 5mA Maximum OFF Current 2mA Base Power Required 5VDC 100mA OFF to ON Response 5 to 30 ms ON to OFF Response 10 to 50 ms Terminal Type included Removable D2 16IOCON Status Indicator Logic side Wei...

Page 84: ...t and 2 Amps per common when using the ZIPLink wiring system At 40mS duration loads of 3 0 A or greater cannot be used At 100mS duration loads of 2 0 A or greater cannot be used Find the load current...

Page 85: ...0ms Base Power Required 5VDC 100mA OFF to ON Response 1ms ON to OFF Response 1ms Terminal Type included Removable D2 8IOCON Status Indicator Logic side Weight 2 3 oz 65g Fuses 1 per common 5A fast blo...

Page 86: ...d Current N A Max Load Current 0 3 A per point 2 4 A per common Max Leakage Current 1 0 mA 40VDC Max Inrush Current 1A for 10ms Base Power Required 5VDC 100mA OFF to ON Response 1ms ON to OFF Response...

Page 87: ...d 5VDC 200mA OFF to ON Response 0 5 ms ON to OFF Response 0 5 ms Terminal Type included Removable D2 16IOCON Status Indicator Logic side Weight 2 3 oz 65g Fuses None ZIPLink Module ZL RTB20 Feedthroug...

Page 88: ...uency N A Minimum Load Current 0 2 mA Max Load Current 0 1 A point 1 6 A module Max Leakage Current 0 1 mA 30VDC Max Inrush Current 150mA for 10ms Base Power Required 5VDC 200mA OFF to ON Response 0 5...

Page 89: ...Terminal type Removable D2 16IOCON Status indicators Logic Side Weight 2 0 oz 25g Fuses None External DC required 24VDC 10 50mA External DC overvoltage shutdown 27V outputs are restored when voltage...

Page 90: ...an be reset by turning the assigned output off or power cycling the PLC Example In this example X8 X23 are assigned as fault status indicators X8 Fault status indicator for Y0 X9 Fault status indicato...

Page 91: ...OFF response 0 5 ms Terminal type Removable D2 16IOCON Status indicators Logic Side Weight 2 0 oz 25g Fuses None External DC required 24VDC 10 50mA External DC overvoltage shutdown 27V outputs are re...

Page 92: ...ycling the PLC In this example X8 X23 are assigned as fault status indicators X8 Fault status indicator for Y0 X9 Fault status indicator for Y1 X22 Fault status indicator for Y14 X23 Fault status indi...

Page 93: ...10ms Base Power Required 5VDC 350mA OFF to ON Response 0 5 ms ON to OFF Response 0 5 ms Terminal Type not included Removable 40 pin connector1 Status Indicator Module activity no I O status indicator...

Page 94: ...g Voltage 12 to 24 VDC Peak Voltage 30VDC ON Voltage Drop 0 5 VDC 0 1 A Minimum Load Current 0 2 mA Max Load Current 0 1 A point 0 8 A common Max Leakage Current 0 1 mA 30VDC Max Inrush Current 150mA...

Page 95: ...Max Load Current 1 5 A pt 30 C 1 0 A pt 60 C 4 0 A common 8 0 A module 60 C Max Leakage Current 0 7 mA rms Peak One Cycle Surge Current 15A Base Power Required 5VDC 250mA OFF to ON Response 0 5 ms 1 2...

Page 96: ...5 A point 4A common Max Leakage Current 4mA 264VAC 60Hz 1 2 mA 100VAC 60Hz 0 9 mA 100VAC 50Hz Max Inrush Current 10A for 10ms Base Power Required 5VDC 250mA OFF to ON Response 1ms ON to OFF Response...

Page 97: ...o n is the starting address Yes Yes Yes Yes Yes Points Yn 10 Yn 11 Yn 12 Yn 13 Yn 14 Yn 15 Yes Used No No 8 Yn Yn 9 Y 0 3 6 9 12 Points 250mA Pt 300mA Pt 0 10 20 30 40 50 55 Ambient Temperature C F 32...

Page 98: ...wer Required 5VDC 250 mA OFF to ON Response 10ms ON to OFF Response 10ms Terminal Type included Removable D2 8IOCON Status Indicator Logic side Weight 2 8 oz 80g Fuses 1 per point 6 3 A slow blow repl...

Page 99: ...ncluded Removable D2 8IOCON Status Indicator Logic side Weight 3 9 oz 110g Fuses One 6 3 A slow blow replaceable Order D2 FUSE 3 5 per pack ZIPLink Module ZL RTB20 Feedthrough ZIPLink Cable ZL D2 CBL1...

Page 100: ...system L L L L L L L L NO1 NO2 NO4 C4 7 NO7 NO0 CO 3 NO3 NO5 NO6 F2 08TR 0 1 2 3 4 5 6 7 OUT RELAY 12 250VAC 10A 50 60Hz 12 28VDC 10mA 10A NO1 NO2 NO4 C4 7 NO7 NO0 CO 3 NO3 NO5 NO6 F2 08TR 0 1 2 3 4...

Page 101: ...ZL RTB20 Feedthrough ZIPLink Cable ZL D2 CBL19 0 5 m ZL D2 CBL19 1 1 0 m ZL D2 CBL19 2 2 0 m ZL D2 CBL19 1P 1 0 m Pigtail ZL D2 CBL19 2P 2 0 m Pigtail F2 08TRS outputs are derated not to exceed 2 Amp...

Page 102: ...Module 12 Outputs Points Consumed 16 four unused see chart below Commons per Module 2 6 pts per common Output Type Relay form A SPST Operating Voltage 5 30 VDC 5 240 VAC Peak Voltage 30VDC 264VAC ON V...

Page 103: ...264VAC ON Voltage Drop N A AC Frequency 47 to 63 Hz Minimum Load Current 5mA 5VDC Max Load Current resistive 1A point 4A module Max Leakage Current 0 1 mA 264VAC Max Inrush Current 3A for 100 ms 10A...

Page 104: ...Do more H2 Series PLC Hardware User Manual 1st Edition Rev F H2 DM M 5 32 Chapter 5 Specifications Discrete I O Modules 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D Notes...

Page 105: ...etting the Module Jumpers 6 7 F2 04AD 1 L Addressing 6 8 F2 04AD 2 L Analog Input 6 9 Setting the Module Jumpers 6 10 F2 04AD 2 L Addressing 6 11 F2 08AD 1 Analog Input 6 12 Setting the Module Jumpers...

Page 106: ...ut 6 41 Setting the Module Jumpers 6 42 F2 4AD2DA Analog Input Output 6 44 Input 6 46 Output 6 46 F2 8AD4DA 1 Analog Input Output 6 47 Input 6 50 Output 6 50 Input Configuration Using Do more Designer...

Page 107: ...the front panel signifies an Input I O module a red bar signifies an Output I O module and a white bar signifies a combination Input Output module Analog Input Modules Part Number Number of Channels D...

Page 108: ...DA 1 OUT ANALOG 2CH F2 02DA1 18 30VDC 60mA ANALOG OUT 4 20mA 24V CH1 CH2 NC NC 0V CH1 CH2 NC NC F2 02DA 1 OUT ANALOG A 2CH F2 02DA1 18 30VDC 60mA ANALOG OUT 4 20mA Module Type Red Output Module Part N...

Page 109: ...ta and setup data X addresses are also assigned to some analog I O modules to indicate the status of those analog I O modules The following table shows how many X WX and WY addresses are assigned to e...

Page 110: ...12 13 14 A B C D Analog I O Modules Overview continued You can check which X WX and WY addresses are assigned to each analog I O module in the I O Mapping tab of the System Configuration window as sh...

Page 111: ...elative Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration MIL STD 810C 514 2 Shock MIL STD 810C 516 2 Noise Immunity NEMA ICS3 304 Terminal Type included Removab...

Page 112: ...o if you only select channels 1 thru 3 channel 4 will not be active The following table shows how to use the jumpers to select the number of channels Unused jumpers can be stored on a single post to p...

Page 113: ...is removed This address stays off if Channel 2 input is not used Xn 2 On when the external 24VDC input power is missing or terminal block is removed This address stays off if Channel 3 input is not u...

Page 114: ...514 2 Shock MIL STD 810C 516 2 Noise Immunity NEMA ICS3 304 Terminal Type included Removable D2 8IOCON ZIPLink Module ZL RTB20 Feedthrough ZIPLink Cable ZL D2 CBL10 0 5 m ZL D2 CBL10 1 1 0 m ZL D2 CBL...

Page 115: ...o prevent losing them As seen above there is also one input signal range jumper labeled J2 or J3 that is used to select between the 5V and 10V signal ranges The module is set from the factory for 10V...

Page 116: ...en the external 24VDC input power is missing or terminal block is removed This address stays off if Channel 2 input is not used Xn 2 On when the external 24VDC input power is missing or terminal block...

Page 117: ...rrosive gases permitted Vibration MIL STD 810C 514 2 Shock MIL STD 810C 516 2 Noise Immunity NEMA ICS3 304 Terminal Type included Removable D2 8IOCON ZIPLink Module ZL RTB20 Feedthrough ZIPLink Cable...

Page 118: ...4 thru eight will not be active The following table shows how to use the jumpers to select the number of channels Unused jumpers can be stored on a single post to prevent losing them F2 08AD 1 Module...

Page 119: ...24VDC input power is missing or terminal block is removed This address stays off if Channel 4 input is not used Xn 4 On when the transmitter is broken the external 24VDC input power is missing or term...

Page 120: ...r Supply 5mA maximum 10 to 30 VDC Operating Temperature 32 to 140 F 0 to 60 C Storage Temperature 4 to 158 F 20 to 70 C Relative Humidity 5 to 95 non condensing Environmental Air No corrosive gases pe...

Page 121: ...seen above there is another jumper labeled J3 that is used to select between the 5V and 10V signal ranges The module is set from the factory for 10V operation jumper not installed F2 08AD 2 Module Ju...

Page 122: ...ddress stays off if Channel 4 input is not used Xn 4 On when the external 24VDC input power is missing or terminal block is removed This address stays off if Channel 5 input is not used Xn 5 On when t...

Page 123: ...racy 1 C PLC Update Rate 4 channels per scan maximum Base Power Required 5VDC 90mA Operating Temperature 32 to 140 F 0 to 60 C Storage Temperature 4 to 158 F 20 to 70 C Temperature Drift None self cal...

Page 124: ...agnitude sign format in Fahrenheit or Celsius Therearetwochannelselectionjumpers labeledCH 1andCH 2 thatareusedtoselectthenumber of channels that will be used The module is set from the factory for fo...

Page 125: ...e RTD Inputs RTD 0 RTD 1 RTD 2 CU 10q No No No CU 25q Yes No No jPt 100q No Yes No Pt 100q Yes Yes No Pt 1000q No No Yes Yes Jumper Installed No Jumper Removed The last two jumpers Units 0 and Units 1...

Page 126: ...ed Xn 1 On when the RTD is open or terminal block is removed This address stays off if Channel 2 input is not used Xn 2 On when the RTD is open or terminal block is removed This address stays off if C...

Page 127: ...2 Shock MIL STD 810C 516 2 Noise Immunity NEMA ICS3 304 Terminal Type included Non removable Thermocouple Specifications Input Ranges Type J 190 to 760 C 310 to 1400 F Type E 210 to 1000 C 346 to 183...

Page 128: ...tem Note 5 With grounded thermocouples take precautions to prevent having a voltage potential between thermocouple tips A voltage of 5V or greater between tips will skew measurements F2 04THM continue...

Page 129: ...set from the factory for four channel operation Any unused channels are not processed The following table shows how to use the jumpers to select the number of channels Unused jumpers can be stored on...

Page 130: ...s The options are 2 s complement in Fahrenheit or Celsius All thermocouple types are converted into a direct temperature reading in either Fahrenheit or Celsius The data contains one implied decimal p...

Page 131: ...s 0 jumper installed for 2 s complement conversion For Fahrenheit remove Units 1 jumper For Celsius remove both Units 0 and Units 1 jumpers The Calibrate Enable jumper J9 comes from the factory in the...

Page 132: ...is module F2 04THM X Addressing Address Description Xn On when the thermocouple is open or the external 24VDC input power is missing Xn 1 On when the thermocouple is open or the external 24VDC input p...

Page 133: ...uding maximum offset change of 2 counts Maximum Inaccuracy 0 1 77 F 25 C 0 3 32 to 140 F 0 to 60 C Base Power Required 5VDC 40mA External Power Supply F2 02DA 1 18 to 30VDC 60mA F2 02DA 1L 10 to 15VDC...

Page 134: ...4 5 6 7 8 9 10 11 12 13 14 A B C D F2 02DA 1 L Analog Output continued The Do more CPU module assigns the following memory addresses to this module WYn Starting WY address assigned to this module F2 0...

Page 135: ...0 55 bipolar ranges 77 F 25 C Base Power Required 5VDC 40mA External Power Supply F2 02DA 2 18 to 30VDC 60mA outputs fully loaded F2 02DA 2L 10 to 15VDC 70mA outputs fully loaded Operating Temperatur...

Page 136: ...rd jumpers are labeled UNI and there is one for each channel These jumpers determine the format of the channel output data and the effect of their settings is independent from that of the other jumper...

Page 137: ...ange the jumpers as follows Install the CH1 UNI 5V jumper Remove the CH1 UNI jumper Store the jumper so it does not get lost by placing it on one pin Install the CH1 BI P 0 5 jumper in the BI P bipola...

Page 138: ...D The Do more CPU module assigns the following memory addresses to this module F2 02DA 2 L Analog Output continued WYn Starting WY address assigned to this module F2 02DA 2 L WY Addressing Address De...

Page 139: ...ontinuous channel to channel channel to logic Base Power Required 5VDC 100mA Loop Supply 18 32 VDC External Power Supply 18 32 VDC 50mA per channel Output Loop Compliance Vin 2 5 V Load Impedance 0 13...

Page 140: ...es is Signed Word They store 32768 to 32767 as default To read and write 0 to 65535 into these memory addresses use the casting U U is the casting for Unsigned format For instance if WY0 is assigned t...

Page 141: ...ling Time 3ms to 0 1 of full scale Linearity Error end to end 10 count 0 015 of full scale maximum Gain Calibration Error 32 counts 0 05 Offset Calibration Error 13 counts 0 02 Output Drift 50ppm C Ma...

Page 142: ...move these jumpers to select the desired range See the figures below to find the jumpers on your module The module is set from the factory for the 0 5 V range Refer to the following table in order to...

Page 143: ...es is Signed Word They store 32768 to 32767 as default To read and write 0 to 65535 into these memory addresses use the casting U U is the casting for Unsigned format For instance if WY0 is assigned t...

Page 144: ...NEMA ICS3 304 Terminal Type included Removable D2 16IOCON ZIPLink Module ZL RTB20 Feedthrough ZIPLink Cable ZL D2 CBL19 0 5 m ZL D2 CBL19 1 1 0 m ZL D2 CBL19 2 2 0 m ZL D2 CBL19 1P 1 0 m Pigtail ZL D2...

Page 145: ...g memory addresses to this module F2 08DA 1 WY Addressing Address Description WYn Channel 1 Output Data 0 to 4095 WYn 1 Channel 2 Output Data 0 to 4095 WYn 2 Channel 3 Output Data 0 to 4095 WYn 3 Chan...

Page 146: ...nversion Settling Time 400 s maximum full scale change 4 5 ms to 9ms for digital out to analog out Linearity Error end to end 1 count 0 025 of full scale maximum Full Scale Calibration Error 12 counts...

Page 147: ...ect between the 0 5 V or 0 10 V operating ranges Refer to the following figure and table for proper selection of voltage range The output data format remains 0 4095 for either voltage range selected U...

Page 148: ...g memory addresses to this module F2 08DA 2 WY Addressing Address Description WYn Channel 1 Output Data 0 to 4095 WYn 1 Channel 2 Output Data 0 to 4095 WYn 2 Channel 3 Output Data 0 to 4095 WYn 3 Chan...

Page 149: ...910q 24V current outputs 620q 18V 1200 q 30 V Active Low pass Filter 3dB 20Hz 2 poles 12dB per octave Linearity Error best fit 1 count 0 025 of full scale maximum Output Settling Time 100 s maximum f...

Page 150: ...ower supply commons are connected Note 4 A Series 217 0 032A fast acting fuse is recommended for 4 20 mA current input loops Note 5 f the power supply common of an external power supply is not connect...

Page 151: ...oved Xn 1 On when the external 24VDC input power is missing or terminal block is removed Xn 2 On when the external 24VDC input power is missing or terminal block is removed Xn 3 On when the external 2...

Page 152: ...utput Protection Electronically current limited to 20mA or less Output Signal at Power up and Power down 4mA Terminal Type included Removable D2 16IOCON ZIPLink Module ZL RTB20 Feedthrough ZIPLink Cab...

Page 153: ...tter 3 wire 4 20mA COM 100 I3 100 100 100 CH5 ADC COM Note 1 A Littlefuse Series 217 0 032A fast acting fuse is recommended for all 4 20mA current loop inputs Note 2 Connect shields to the 0V of the m...

Page 154: ...wer is missing or terminal block is removed Xn 1 On when the transmitter is broken the external 24VDC input power is missing or terminal block is removed Xn 2 On when the transmitter is broken the ext...

Page 155: ...ng U U is the casting for Unsigned format For instance if WY0 is assigned to the first analog output channel use WY0 U to access this memory address in the ladder program and other tools in Do more De...

Page 156: ...aximum or Reset held value or each input can be individually disabled From the System Configurations page select Module Configuration s in the tab on the left The screen below will appear showing the...

Page 157: ...dule Two 2 bits in this memory address are assigned to each analog input channel The HEX data format is used to set up the input resolution as seen in the following example Example An F2 8AD4DA 1 is i...

Page 158: ...The HEX data format is used to set up the track and hold option as seen in the following example Example An F2 8AD4DA 1 is installed in slot 0 and WY6 is used for the track and hold selection Input ch...

Page 159: ...tion 1VDC peak output voltage clamped by transient voltage suppressor Output Signal at Power up and Power down 0V Terminal Type included Removable D2 16IOCON ZIPLink Module ZL RTB20 Feedthrough ZIPLin...

Page 160: ...Isolated analog circuit common Voltage transmitter transmitter 3 wire voltage COM V3 CH5 ADC COM Note 1 Connect shields to the 0V of the module do not connect both ends of shield CH1 DAC CH2 DAC COM C...

Page 161: ...t resolution for the first analog input channel and WX0 is assigned to the channel use WX0 U to access this memory address in the ladder program and other tools in Do more Designer Xn Starting X addre...

Page 162: ...e casting for Unsigned format For instance if WY0 is assigned to the first analog output channel use WY0 U to access this memory address in the ladder program and other tools in Do more Designer WYn S...

Page 163: ...value or each input can be individually disabled Input and output ranges can also be configured for 0 to 5V or 0 to 10V in this section From the System Configurations page select Module Configuration...

Page 164: ...dule Two 2 bits in this memory address are assigned to each analog input channel The HEX data format is used to set up the input resolution as seen in the following example Example An F2 8AD4DA 2 is i...

Page 165: ...is stored in memory address WYn 5 WYn Starting WY address assigned to this module Only 2 bits in this memory address are used for the setup The HEX data format is used to set up the input resolution...

Page 166: ...The HEX data format is used to set up the track and hold option as seen in the following example Example An F2 8AD4DA 2 is installed in slot 0 and WY6 is used for the track and hold selection Input ch...

Page 167: ...H2 CTRIO 2 Input Wiring Examples 7 10 TTL Quadrature Encoder Field Wiring 7 10 TTL Input Wiring Example 7 10 Quadrature Encoder Wiring Example 7 11 NPN Open Collector Device 7 11 PNP Open Collector D...

Page 168: ...BC100 Specifications 7 22 H2 EBC100 LED Indicators 7 23 H2 ERM 100 H2 EBC100 Network Identifiers 7 23 H2 ERM 100 H2 EBC100 Network Layouts 7 26 H2 ERM 100 H2 EBC100 Network Cabling 7 27 H2 SERIO 4 7 2...

Page 169: ...cators can show the network health module health I O status or mode of operation the module is currently in Module Type White Specialty Module Part Number Specialty Modules Part Number Description See...

Page 170: ...unication Module H2 EBC F 10 Base FL Ethernet Base Controller H2 ECOM100 100 Base T Ethernet Communication Module H2 SERIO Serial I O Module H2 ECOM F 10 Base FL Ethernet Communication Module H2 SERIO...

Page 171: ...r a combination of both high speed input and high speed output control functions The H2 CTRIO 2 module has its own internal microprocessor and operates asynchronously with respect to the CPU Therefore...

Page 172: ...nfigure the input and output functions of the selected module Refer to the Do more Designer Help File for more information on configuration options The above window can be accessed once the H2 CTRIO2...

Page 173: ...2 0 mA OFF to ON Response less than 3 s less than 0 5 s ON to OFF Response less than 3 s less than 0 5 s Output Specifications Specifications H2 CTRIO H2 CTRIO2 Outputs 4 pts sink source independentl...

Page 174: ...put is passing current CTR IN OK ER 1A 2A 0 1 2 3 H2 CTRIO 24 VDC OUTPUTS 2A 2B 2C 2D 2M C2 Y2 C3 Y3 1A 1B 1C 1D 1M NC C0 Y0 C1 Y1 IN 9 30 VDC 5 12 mA OUT 5 36 VDC 1 0Amax per point CTR IN OK ER 1A 2A...

Page 175: ...opriate Y0 Y1 Install jumper s to internally connect Y0 to other Y terminals in order to reduce wiring if appropriate Connect wire at Y0 Y0 Y2 Y0 Y3 C0 C1 Install jumper s to internally connect C0 to...

Page 176: ...te wiring to avoid any runs parallel to noisy cables Route wiring to avoid the proximity of noisy devices Use shielded twisted pair cables such as 24VDC 1A 1M Sensing Circuit This drawing illustrates...

Page 177: ...0 V Black OUT A Purple OUT A White OUT B Gray OUT B Orange OUT Z Yellow OUT Z Shield Ground Differential Line Driver Encoder Use separate power supply to maintain isolation CTR IN 24 VDC OUTPUTS IN 9...

Page 178: ...2 Y 3 C 3 Y M 2 A B Z 9 30VDC 9 30VDC Power Gnd A B Z Power Gnd NPN Open Collector PNP Open Collector or Totem Pole Quadrature Encoder Wiring Example NPN Open Collector Device Encoder Shield twisted p...

Page 179: ...a standard method but you must consult your step amplifier documentation to ensure that this method is applicable 5 to 36VDC CTRIO Output Cn where n 0 1 2 3 Yn where n 0 1 2 3 Load 5 to 36VDC Load CT...

Page 180: ...and MODBUS TCP IP devices is accomplished by using the MRX MWX instructions You can use a personal computer equipped with a 10 100BaseT network adapter card and NetEdit3 software to configure the ECO...

Page 181: ...ON Green Properly connected to network OFF Not connected to network or incorrect configuration ACTIVE ON or FLASHING Red Active Network Data OFF Network Idle ERROR ON or FLASHING Red A fatal error ha...

Page 182: ...e diagram below The Name can be up to 32 alphanumeric characters in length NOTE Some HMI software products will not accept Names with numbers as the first character spaces or certain other non alphanu...

Page 183: ...ddresses must match the first two fields of the Client IP or 192 168 The last two fields are allowed to vary because they are masked with a 0 WARNING It is extremely important not to have duplicate IP...

Page 184: ...mmunication with the PC An ECOM can sequence through communication connections with each PLC on the network one at a time The ECOM products inherently support two network layouts point to point and st...

Page 185: ...tch straight through cable The cable used to connect together two PLCs a PC and a PLC or two switches is a crossover cable We recommend that you purchase cables pre assembled with connectors for conve...

Page 186: ...Therefore it is not possible to state an absolute maximum number of nodes that would apply in all cases The IEEE 802 3 specification defines the maximum node limit for an Ethernet segment in terms of...

Page 187: ...ECOM modules you can access from the NetEdit3 or Do more Designer software There is a node limit for PLC to PLC communications The network Read and Write instructions performed by the initiating maste...

Page 188: ...pand the number of nodes The PLC ERM and EBC slave modules work together to update the remote I O points These three scan cycles are occurring at the same time but asynchronously Critical I O points t...

Page 189: ...odule supports industry standard 10 100BaseT Ethernet and Ethernet IP communications NOTE The RS 232 serial port on the EBC module cannot be used when the EBC module is part of the Do more controller...

Page 190: ...ERM to 0 Module ID can be changed without NetEdit3 When set disables Module ID selection in NetEdit3 NetEdit3 Slave Number 1 65535 Set ERM to 0 DIP Switch must be set to 0 IP Address UDP IP NetEdit3 4...

Page 191: ...le if slide switches 1 2 and 3 are set to the ON position the Module ID will be 14 This is found by adding 8 4 2 14 The maximum value which can be set on the DIP switch is 32 16 8 4 2 63 This is achie...

Page 192: ...55 fields If any field contains the number 255 and other fields have been changed the module will not be recognized on the network Example IP Addresses 192 168 55 5 Valid IP Address 255 168 55 5 Not V...

Page 193: ...he ERM module and its slaves over the Ethernet remote I O network Once the ERM I O network is configured and running the PC can be removed from the network 405EBC POWER ERROR RELAY LINK GOOD ACTIVITY...

Page 194: ...ch is called a patch straight through cable The cable used to connect together two PLCs a PC and a PLC or two switches is a crossover cable We recommend that you purchase cables pre assembled with con...

Page 195: ...12 13 14 A B C D The maximum distance per 10 100BaseT cable segment is 100 meters or 328 feet Switches allow multiple 100 meter cable segments to be joined together increasing the allowable distance F...

Page 196: ...n to setup the port to work with the Do more Designer programming software K Sequence Select this option to have the port respond to client devices running K Sequence protocol Modbus RTU Server Select...

Page 197: ...M 7 31 Chapter 7 Specifications Specialty Modules 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D These parameters can also be set programmatically using the SETUPSER instruction seen here See the Do more He...

Page 198: ...422 ADC L19853 x Belden 8103 RS 485 ADC L19954 x Belden 9842 Protocols Supported Serial ASCII full duplex K Sequence Modbus RTU and Do more programming Power Consumption 80mA 5VDC Baud Rates 1200 240...

Page 199: ...ate or deactivate resistor GND RX RX TX TX Slave 2 D RXD D RXD Set DIP switch S2 on the H2 SERIO 4 to 1 Activate or deactivate the internal 120 termination resistor 2 Select RS 422 or RS 485 operation...

Page 200: ...alty Modules 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D F2 08SIM Input Simulator F2 08SIM Specifications F2 08SIM Input Simulator Inputs per Module 8 Base Power Required 5VDC 50mA Terminal Type None Sta...

Page 201: ...se Dimensions 8 5 Panel Mounting and Layout 8 6 Enclosures 8 7 Environmental Specifications 8 8 Marine Use 8 8 Agency Approvals 8 8 24VDC Power Bases 8 8 Installing Bases for Do more 8 9 Mounting the...

Page 202: ...es 8 17 Powering I O Circuits with the Auxiliary Supply 8 18 Powering I O Circuits Using Separate Supplies 8 19 Sinking Sourcing Concepts 8 20 I O Common Terminal Concepts 8 21 Connecting DC I O to So...

Page 203: ...ts should be designed using simple logic with a minimum number of highly reliable electromechanical components Every automation application is different so there may be special requirements for your p...

Page 204: ...should be easily accessed by the operator and are generally wired into a master control relay MCR or a safety control relay SCR that will remove power from the PLC I O system in an emergency MCRs and...

Page 205: ...ally the first level of fault detection is the PLC control program which can identify machine problems Certain shutdown sequences should be performed The types of problems are usually things such as j...

Page 206: ...tion shows the proper mounting dimensions The height dimension is the same for all bases The depth varies depending on your choice of I O module The length varies as the number of slots increase Make...

Page 207: ...provide proper ventilation 2 If you place more than one base in a cabinet there should be a minimum of 7 2 in 183mm between bases 3 Provide a minimum clearance of 2in 50mm between the base and all si...

Page 208: ...rature may approach the lower or upper limits of the specifications Place a temperature probe in the panel close the door and operate the system until the ambient temperature has stabilized If the amb...

Page 209: ...s which your application may require are UL Underwriters Laboratories Inc CSA Canadian Standards Association FM Factory Mutual Research Corporation cUL Canadian Underwriters Laboratories Inc 24VDC Pow...

Page 210: ...ils are approximately 35mm high with a depth of 7 5 mm If you mount the base on a rail you should also consider using end brackets on each end of the rail The end brackets help keep the base from slid...

Page 211: ...he module is inserted into the base push in the retaining clips to firmly secure the module to the base WARNING To minimize the risk of electrical shock personal injury or equipment damage always disc...

Page 212: ...the recommended size Do not overtighten the connector screws the recommended torque value is 7 81 lb in 0 882 N m NOTE You can connect either a 115VAC or 220VAC supply to the AC terminals without the...

Page 213: ...troller and is not numbered Module Placement Restrictions The following table lists the valid locations for all types of modules in a Do more system Module Unit Local CPU Base Ethernet Remote I O Base...

Page 214: ...sily removed If you examine the connectors closely you ll notice there are squeeze tabs on the top and bottom To remove the terminal block press the squeeze tabs and pull the terminal block away from...

Page 215: ...where possible 5 Avoid running wires near high energy wiring Also avoid running input wiring close to output wiring where possible 6 To minimize voltage drops when wires must run a long distance cons...

Page 216: ...dule Cable F2 04AD 1 10 Feedthrough ZL RTB20 ZL D2 CBL10 F2 08AD 1 10 Feedthrough ZL RTB20 ZL D2 CBL10 F2 04AD 2 10 Feedthrough ZL RTB20 ZL D2 CBL10 F2 08AD 2 10 Feedthrough ZL RTB20 ZL D2 CBL10 F2 02...

Page 217: ...D2 CBL19 Fuse ZL RFU204 ZL D2 CBL19 D2 04TRS 10 Feedthrough ZL RTB20 ZL D2 CBL10 D2 08TR 10 Feedthrough ZL RTB20 ZL D2 CBL10 F2 08TRS 19 Feedthrough ZL RTB20 ZL D2 CBL19 F2 08TR 10 Feedthrough ZL RTB2...

Page 218: ...crete inputs are isolated from the discrete outputs because each is isolated from the logic side Isolation boundaries protect the operator interface and the operator from power input faults or field w...

Page 219: ...y supply If input devices AND output loads need 24VDC power the auxiliary supply may be able to power both circuits as shown in the following diagram The 12 24VDC powered bases are designed for applic...

Page 220: ...ions will use the PLC external power source to also power the input circuit This typically occurs on DC powered PLCs as shown in the drawing below to the left The inputs share the PLC power source sup...

Page 221: ...le to connect the external supply and field device to the I O point with current trying to flow in the wrong direction and the circuit will not operate However you can successfully connect the supply...

Page 222: ...hare a common return path In this way the four inputs require only five terminals instead of eight NOTE In the circuit above the current in the common path is 4 times any channel s input current when...

Page 223: ...n be the 24 auxiliary supply or another supply 12 VDC or 24VDC as long as the input specifications are met In the above circuit a field device has an open collector PNP transistor output It sources cu...

Page 224: ...rehend this and generate an inverted output Or you may choose to cancel the effect of the inversion elsewhere such as in the field device It is important to choose the correct value of Rpull up In ord...

Page 225: ...uire currents under 10mA Loads which must be switched at high speed or heavy duty cycle Relay outputs in the Do more output modules are available in two contact arrangements shown to the right The For...

Page 226: ...s opened thereby de energizing the coil the transient voltage generated across the switch contacts peaks at 140V In the same circuit replacing the relay with a larger 24V 290mA 7W relay will generate...

Page 227: ...range for some time the 40V is still beyond the module s peak output voltage rating of 30V 5HOD RLO 9 2VFLOORVFRSH RU WKLV H DPSOH D 9 P UHOD LV XVHG XWRPDWLRQ LUHFW SDUW QR 9ROWV Example Small Induct...

Page 228: ...ope 24 VDC DC Flyback Circuit Sinking Sourcing _ 30 25 20 15 10 5 0 5 Volts Many AutomationDirect socketed relays and motor starters have add on flyback diodes that plug or screw into the base such as...

Page 229: ...check the suppressor ratings Just because the suppressor is made specifically for that part does not mean it will reduce the transient voltages to an acceptable level For example a MOV or TVS diode ra...

Page 230: ...Do more H2 Series PLC User Manual 1st Edition Rev F H2 DM M 8 30 Chapter 8 Installation and Wiring 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D Notes...

Page 231: ...Do more Product Weight Table A A A Appendix Appendix Appendix In This Appendix Do more Product Weight Table A 2...

Page 232: ...80g D2 08TD1 2 3 oz 65g D2 08TD2 2 1 oz 60g D2 16TD1 2 2 3 oz 65g D2 16TD2 2 2 8 oz 80g F2 16TD1P 2 0 oz 56g F2 16TD2P 2 0 oz 56g D2 32TD1 2 1oz 60g D2 32TD2 2 1 oz 60g AC Output Modules D2 08TA 2 8...

Page 233: ...European Union Directives CE Appendix Appendix Appendix B B In This Appendix European Union EU Directives B 2 Basic EMC Installation Guidelines B 5...

Page 234: ...alta Netherlands Poland Portugal Romania Slovakia Slovenia Spain Sweden and United Kingdom Iceland Liechtenstein and Norway together with the EU members make up the European Economic Area EEA and all...

Page 235: ...al commercial and light industry EN50082 2 Generic immunity standard for industrial environment Low Voltage Directive Standards Applicable to PLCs EN61010 1 Safety requirements for electrical equipmen...

Page 236: ...rictions on the control panel builder Because of these additional requirements it is recommended that the following publications be purchased and used as guidelines BSI publication BS TH 42073 Novembe...

Page 237: ...d like to point out that although our products operate normally in the presence of ESD this is only the case when mounted within an enclosed industrial control cabinet When the cabinet is open during...

Page 238: ...l supplies 150VAC working voltage for 115V supplies and high energy capacity eg 140 joules Transient suppressors must be protected by fuses and the capacity of the transient suppressor must be greater...

Page 239: ...ices connected to the PLC The diagram shows an example of four physical locations connected by a communications cable Communications and Shielded Cables Good quality 24 AWG minimum twisted pair shield...

Page 240: ...n provided in the past by the cable shield It is now recommended that you use triple twisted pair cabling for RS422 links and twin twisted pair cable for RS485 links This is because the extra pair can...

Page 241: ...g maintenance so that remote commands cannot be received that could result in the operation of the machinery The FA ISOCON does not have a keyswitch Use a keylock and switch on your enclosure which wh...

Page 242: ...n a protective steel enclosure which limits access to operators by a lock and power breaker If access is required by operators or untrained personnel the equipment must be installed inside an internal...

Reviews: