Do-more H2 Series PLC User Manual, 1st Edition, Rev. F - H2-DM-M
6–32
Chapter 6: Specifications - Analog I/O Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
The F2-02DA-2(L) Analog Output module uses jumpers for selecting the voltage ranges for
each channel. The range of each channel can be independently set. Available operating ranges
are 0–5 V, 0–10 V,
±
5V, and
±
10V. There are three jumpers for each channel. Two sets are
on the top board, and the third set is along the edge of the bottom board with the black D-shell
backplane connector. Install or remove these jumpers to select the desired range.
•
Two of the top board jumpers are
labeled “UNI/
±
5” and there is one for
each channel. These jumpers are used
in conjunction with the “BI-P 0-5”
jumpers to determine output voltage
polarity and range.
•
The two bottom board jumpers are
labeled “UNI” and there is one for each
channel. These jumpers determine the
format of the channel output data, and
the effect of their settings is independent
from that of the other jumpers on the
module. With a UNI jumper removed,
the corresponding channel requires data
values in the range of
±
2047. With a
UNI jumper installed, the channel
requires data values in the range of 0 to
4095.
• The other two top board jumpers are
labeled “BI-P 0-5” and there is one for
each channel. These jumpers are used in
conjunction with the “UNI/
±
5” jumpers
to determine output voltage polarity and
range.
NOTE: It is important to set the module jumpers correctly. The module will not operate correctly if the
jumpers are not properly set for the desired voltage range.
F2-02DA-2(L), Analog Output - continued
CH1-UNI
CH2-UNI
UNI / ±5
CH1
UNI / ±5
CH2
CH1
BI-P
BI-P
0-5V
CH2
0-5V
Three
positions
available
Bipolar (BI-P)
Position
1
0-5V
Position
2
0-10V
Position
3
(Jumper is
shown on a
single pin; this
is the factory
setting)