Do-more H2 Series PLC User Manual, 1st Edition, Rev. F - H2-DM-M
6–5
Chapter 6: Specifications - Analog I/O Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Analog I/O Modules Overview- continued
How to Access the Analog I/O Modules
With the Do-more PLC, the WX and WY memory addresses are assigned to exchange analog
data with the analog I/O modules. (WX = Analog input data, WY = Analog output data and
setup data) X addresses are also assigned to some analog I/O modules to indicate the status
of those analog I/O modules.
The following table shows how many X, WX and WY addresses are assigned to each analog
I/O module type.
Analog Input/Output Module Addressing
Part Number
Module ID
X
WX
WY
F2-04AD-1
0x3E
8
4
-
F2-04AD-2
0x3E
8
4
-
F2-08AD-1
0x3B
8
8
-
F2-08AD-2
0x3B
8
8
-
F2-04RTD
0x3C
8
4
-
F2-04THM
0x3C
8
4
-
F2-02DA-1(L)
0x3F
-
-
2
F2-02DA-2(L)
0x3F
-
-
2
F2-02DAS-1
0x4E
-
-
2
F2-02DAS-2
0x4E
-
-
2
F2-08DA-1
0x4F
-
-
8
F2-08DA-2
0x4F
-
-
8
F2-4AD2DA
0x3D
8
4
2
F2-8AD4DA-1
0x37
8
8
7
F2-8AD4DA-2
0x37
8
8
7