Do-more H2 Series PLC User Manual, 1st Edition, Rev. F - H2-DM-M
8–12
Chapter 8: Installation and Wiring
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Base Wiring Guidelines
Base Wiring
The following diagrams show the terminal
connections located on the power supply of the
Do-more bases. The base terminals can accept up
to 16 AWG. You may be able to use larger wiring
depending on the type of wire used, but 16 AWG
is the recommended size. Do not overtighten
the connector screws; the recommended torque
value is 7.81 lb·in (0.882 N·m).
NOTE:
You can connect either a 115VAC or 220VAC supply to the AC terminals without the need of special
wiring or jumpers.
WARNING: Once the power wiring is connected, install the plastic protective cover. When the cover is
removed there is a risk of electrical shock if you accidentally touch the wiring or wiring terminals.
125 VDC Base T erminal Strip
12/24 VDC Base T erminal Strip
G
10.2 – 28.8 VDC
+
–
1 20 – 240 VDC
G
24 VDC OUT, 0.3A
–
+
LG
–
+
1 10/220 V AC Base T erminal Strip
100 – 240 VAC
G
24 VDC OUT, 0.3A
LG
+