Do-more H2 Series PLC Hardware User Manual, 1st Edition, Rev. F - H2-DM-M
1–12
Chapter 1: Getting Started
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Step 4: Apply Power to the Do-more! PLC
Power is supplied to the Do-more! PLC through the backplane of the base from the power
supply. The following diagrams show the terminal connections located on the power supplies
of the DL205 bases. The base terminals can accept up to 16AWG. You may be able to use
larger wiring depending on the type of wire used, but 16AWG is the recommended size. Do not
over-tighten the connector screws; the recommended torque value is 7.81 lb·in (0.882 N·m).
NOTE:
You can connect either a 115VAC or 220VAC supply to the AC terminals.
Once all of the power wiring has been completed and verified, connect the appropriate
voltage source to the power supply and power up the controller. The Do-more PLC will
perform a self evaluation once power is applied. Refer to the “Installation and Wiring”
chapter of this manual for more power supply and input wiring information.
125 VDC Base T erminal Strip
12/24 VDC Base T erminal Strip
G
10.2 – 28.8 VDC
+
–
1 20 – 240 VDC
G
24 VDC OUT, 0.3A
–
+
LG
–
+
1 10/220 V AC Base T erminal Strip
100 – 240 VAC
G
24 VDC OUT, 0.3A
LG
+