Do-more H2 Series PLC Hardware User Manual, 1st Edition, Rev. F - H2-DM-M
5–5
Chapter 5: Specifications - Discrete I/O Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
D2-08ND3, DC Input
D2-08ND3 DC Input
Inputs per Module
8 (sink/source)
Commons per Module
1 (2 I/O terminal points)
Input Voltage Range
10.2-26.4 VDC
Peak Voltage
26.4 VDC
ON Voltage Level
9.5 VDC minimum
OFF Voltage Level
3.5 VDC maximum
AC Frequency
N/A
Input Impedance
2.7 k
q
Input Current
4.0 mA @ 12VDC
8.5 mA @ 24VDC
Minimum ON Current
3.5 mA
Maximum OFF Current
1.5 mA
Base Power Required 5VDC
50mA
OFF to ON Response
1 to 8 ms
ON to OFF Response
1 to 8 ms
Terminal Type (included)
Removable, D2-8IOCON
Status Indicator
Logic side
Weight
2.3 oz. (65g)
ZIPLink Module
ZL-RTB20 (Feedthrough)
ZIPLink Cable
ZL-D2-CBL10 (0.5m)
ZL-D2-CBL10-1 (1.0m)
ZL-D2-CBL10-2 (2.0m)
0
2
4
6
8
0
1 0
2 0
3 0
4 0
5 0 5 5
A m b i e n t T e m p e r a t u r e ( ° C / ° F )
3 2
5 0
6 8
8 6
1 0 4
1 2 2 1 3 1
C
°
F
°
D e r a t i n g C h a r t
P o i n t s
C
C
0
1
2
3
4
5
6
7
12--24VDC
Internally
connected
+ -
+
-
Sink
Source
Optical
COM
Isolator
INPUT
12--24VDC
V+
To LE D
Internal module circuitry
COM
+
+
-
-
Sink
Source
C
4
5
6
7
0
1
2
3
10.2-26.4VDC
4-12mA
C
D2-08ND3
IN
12-24
VDC
0
1
2
3
4
5
6
7
C
4
5
6
7
0
1
2
3
10.2-26.4VDC
4-12mA
C
D2-08ND3
IN
12-24
VDC
0
1
2
3
4
5
6
7