Before starting any maintenance or repairs, wait until the compressor has
stopped and open the isolating switch (customer's installation) to switch off the
voltage to the compressor.
Close the air outlet valve and open the manual condensate drain valves to
depressurize the air system.
Apply all relevant
5.6
External compressor status indication
Warning
Stop the compressor and switch off the voltage before connecting external equipment.
Consult the
Connections for external compressor status indication
Terminal strip (1X7) is fitted with auxiliary contacts for external indication of:
Indication
Relay
Terminals on strip 1X1
Maximum load
Automatic operation
K07
11-12
10 A / 230 V AC
Warning
K08
13-14
10 A / 230 V AC
Shut-down
K09
15-16
10 A / 230 V AC
Compressor loaded
K11
19-20
10 A / 230 V AC
Compressor running
K21
17-18
10 A / 230 V AC
5.7
Control programs
Description
In order to facilitate programming and controlling, menu-driven control programs have been implemented
in the regulator.