![Atlas Copco ZR 110 Instruction Book Download Page 167](http://html.mh-extra.com/html/atlas-copco/zr-110/zr-110_instruction-book_3001728167.webp)
Unit
Min.
(Pack
version)
Min.
(Full-
Feature
version)
Max.
Max. (with
Energy
Recovery)
* 125 psi (60 Hz)
58.0
94.3
124.8
117.6
* 145 psi (50 Hz)
101.5
108.8
145.1
137.9
* 150.8 psi (60 Hz)
101.5
108.8
150.9
143.7
* 188.5 psi (50 Hz)
101.5
137.8
188.6
181.4
* 188.5 psi (60 Hz)
101.5
137.8
188.6
181.4
Control timers
s
Unload time
3
3
20
20
Minimum stop time
20
20
99
99
Y-D starter
s
Y-D time
10
10
30
30
Y-D time with motor voltage > or = 2.3 kV
0
0
30
30
Load delay
3
3
30
30
Load delay with motor voltage > or = 2.3 kV
13
13
30
30
Automatic Restart After Voltage Failure - ARAVF
s
Maximum power down time
20
20
3600
3600
Restart delay
0
0
255
255
Others
s
External communication timeout
10
10
60
60
6.19 Web server
All controllers have a built-in web server that allows direct connection to the company network or to a
dedicated PC via a local area network (LAN). This allows to consult certain data and settings via a PC
instead of the display of the controller.
Getting started
If the unit is equipped with a
SMART
BOX, the network connection of the Elektronikon is
already in use. To allow the web server functionality, the network cable that is
connected to the
SMART
BOX should be unplugged and replaced by the cable of the
company network.
If both the web server functionality and
SMART
BOX are required, please contact your
local Atlas Copco Customer Center for support.
Make sure you are logged in as administrator.
• Use the internal network card from your computer or a USB to LAN adapter.
Instruction book
2920 1815 04
165
Summary of Contents for ZR 110
Page 2: ......
Page 179: ...Dimension drawing of ZT 110 up to ZT 145 page 1 Instruction book 2920 1815 04 177 ...
Page 214: ... CORRECT installation Instruction book 212 2920 1815 04 ...
Page 249: ...Electric cabinet of compressor with starter Model year 2014 Instruction book 2920 1815 04 247 ...
Page 326: ......
Page 327: ......