![Atlas Copco ZR 110 Instruction Book Download Page 310](http://html.mh-extra.com/html/atlas-copco/zr-110/zr-110_instruction-book_3001728310.webp)
Supply voltage
(V)
Recommended overload setting F21
(A)
380
187
440
163
460
161
575
127
ZR/ZT 160 compressors designed for a maximum inlet temperature of 40 ˚C/104 ˚F with IE3 motor
Supply voltage
(V)
Recommended overload setting F21
(A)
380
194
440
166
460
163
575
131
ZR/ZT 160 compressors designed for a maximum inlet temperature of 50 ˚C/122 ˚F with IE2 motor
or equipped with oversized IE2 motor
Supply voltage
(V)
Recommended overload setting F21
(A)
380
236
440
204
460
209
575
167
ZR/ZT 160 compressors designed for a maximum inlet temperature of 50 ˚C/122 ˚F with IE3 motor
or equipped with oversized IE3 motor
Supply voltage
(V)
Recommended overload setting F21
(A)
380
219
440
187
460
181
575
146
ZR/ZT 200 compressors designed for a maximum inlet temperature of 40 ˚C/104 ˚F with IE2 motor
Supply voltage
(V)
Recommended overload setting F21
(A)
380
236
440
204
460
209
575
167
ZR/ZT 200 compressors designed for a maximum inlet temperature of 40 ˚C/104 ˚F with IE3 motor
Instruction book
308
2920 1815 04
Summary of Contents for ZR 110
Page 2: ......
Page 179: ...Dimension drawing of ZT 110 up to ZT 145 page 1 Instruction book 2920 1815 04 177 ...
Page 214: ... CORRECT installation Instruction book 212 2920 1815 04 ...
Page 249: ...Electric cabinet of compressor with starter Model year 2014 Instruction book 2920 1815 04 247 ...
Page 326: ......
Page 327: ......