Astraada DRV-24 frequency inverters Function Parameters
51
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
P05.36
AI1 input
filter time
The figure below illustrates different
applications:
Input filter time: this parameter is used to
adjust the sensitivity of the analog input.
Increasing the value properly can enhance the
anti-interference of the analog, but weaken the
sensitivity of the analog input
Note: AI1 supports 0~10V input and AI2
supports 0~10V or 0~20mA input, when AI2
selects 0~20mA input, the corresponding
voltage of 20mA is 10V. AI3 can support the
output of -10V~+10V.
The setting range of P05.32:0.00V~P05.34
The setting range of P05.33:-100.0%~100.0%
The setting range of P05.34:P05.32~10.00V
The setting range of P05.35:-100.0%~100.0%
The setting range of P05.36:0.000s~10.000s
The setting range of P05.37:0.00V~P05.39
The setting range of P05.38:-100.0%~100.0%
The setting range of P05.39:P05.37~10.00V
The setting range of P05.40:-100.0%~100.0%
The setting range of P05.41:0.000s~10.000s
The setting range of P05.42:-10.00V~P05.44
The setting range of P05.43:-100.0%~100.0%
The setting range of P05.44:P05.42~P05.46
The setting range of P05.45:-100.0%~100.0%
The setting range of P05.46:P05.44~10.00V
The setting range of P05.48:0.000s~10.000s
0.100s
○
P05.37
Lower limit
of
AI2
0.00V
○
P05.38
Correspondi
ng setting
of the lower
limit of AI2
0.0%
○
P05.39
Upper limit
of AI2
10.00V
○
P05.40
Correspondi
ng setting
of
the upper
limit of AI2
100.0%
○
P05.41
AI2 input
filter time
0.100s
○
P05.42
Lower limit
of
AI3
-10.00
V
○
P05.43
Correspondi
ng setting
of the lower
limit of AI3
-100.0
%
○
P05.44
Middle
value of AI3
0.00V
○
P05.45
Correspondi
ng middle
setting of
AI3
0.0%
○
P05.46
Upper limit
of AI3
10.00V
○
P05.47
Correspondi
ng setting
of
the upper
limit of AI3
100.0%
○
P05.48
AI3 input
filter time
0.100s
○
P05.50
Lower limit
frequency
of HDI
0.000kHz~P05.52
0.000
kHz
○
P05.51
Correspondi
ng setting
of HDI low
frequency
-100.0%~100.0%
0.0%
○
Summary of Contents for AS24DRV4075