Astraada DRV-24 frequency inverters Function Parameters
29
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
8:MODBUS communication setting
The frequency is set by MODBUS
communication. See P14 for detailed
information.
9~11: Reserved
P00.08
B frequency
command
reference
selection
0:Maximum output frequency, 100% of B
frequency setting corresponds to the
maximum output frequency
1: A frequency command, 100% of B frequency
setting corresponds to the maximum output
frequency. Select this setting if it needs to
adjust on the base of A frequency command.
0
○
P00.09
Combinatio
n of the
setting
source
0: A, the current frequency setting is A
frequency command
1: B, the current frequency setting is B
frequency command
2: A+B, the current frequency setting is A
frequency c B frequency command
3: A-B, the current frequency setting is A
frequency command - B frequency command
4: Max (A, B): The bigger one between A
frequency command and B frequency is the set
frequency.
5: Min (A, B): The lower one between A
frequency command and B frequency is the set
frequency.
Note:The combination manner can be shifted
by P05 (terminal function)
0
○
P00.10
Keypad set
frequency
When A and B frequency commands are
selected as “keypad setting”, this parameter
will be the initial value of inverter reference
frequency
Setting range:0.00 Hz~P00.03 (the Max.
frequency)
50.00H
z
○
P00.11 ACC time 1
ACC time means the time needed if the inverter
speeds up from 0Hz to the Max. One (P00.03).
DEC time means the time needed if the inverter
speeds down from the Max. Output frequency
to 0Hz (P00.03).
Astraada DRV-24 series inverters have four
groups of ACC/DEC time which can be selected
by P05. The factory default ACC/DEC time of
the inverter is the first group.
Setting range of P00.11 and
P00.12:0.0~3600.0s
Depen
d on
model
○
P00.12 DEC time 1
Depen
d on
model
○
P00.13
Running
direction
0: Runs at the default direction, the inverter
runs in the forward direction. FWD/REV
0
○