Astraada DRV-24 frequency inverters Function Parameters
42
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
constant
power zone
the steeper the weak curve is.
The setting range of P03.22:0.1~2.0
The setting range of P03.23:10%~100%
P03.24
Max.
voltage limit
P03.24 set the Max. Voltage of the inverter,
which is dependent on the site situation.
The setting range:0.0~120.0%
100.0%
◎
P03.25
Pre-exciting
time
Pre-activate the motor when the inverter starts
up. Build up a magnetic field inside the motor
to improve the torque performance during the
starting process.
The setting time:0.000~10.000s
0.300s
○
P03.26
Weakenin
g
proportion
al gain
0~8000
1200
○
P03.27
Speed
display
selection
of vector
control
0: Display at the actual value
1: Display at the setting value
0
○
P04 Group SVPWM control
P04.00 V/F curve
setting
These function codes define the V/F curve of
Astraada DRV-24 motor 1 to meet the need of
different loads.
0:Straight line V/F curve
;
applying to the
constant torque load
1: Multi-dots V/F curve
2: 1.3th power low torque V/F curve
3: 1.7th power low torque V/F curve
4: 2.0th power low torque V/F curve
Curves 2~4 apply to the torque loads such as
fans and water pumps. Users can adjust
according to the features of the loads to get
the best performance.
5:Customized V/F(V/F separation); in this
mode, V can be separated from f and f can be
adjusted through the frequency given channel
set by P00.06 or the voltage given channel set
by P04.27 to change the feature of the curve.
Note: V
b
in the below picture is the motor
rated voltage and f
b
is the motor rated
frequency.
0
◎