Astraada DRV-24 frequency inverters Function Parameters
72
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
speed 0
the Max. Frequency P00.03.
When selecting simple PLC running, set
P10.02~P10.33 to define the running frequency
and direction of all stages.
Note: The symbol of multi-step determines the
running direction of simple PLC. The negative
value means reverse rotation.
multi-step speeds are in the range of --f
max
~f
max
and it can be
Astraada DRV-24 series inverters can set 16
stages speed, selected by the combination of
multi-step terminals 1~4, corresponding to the
speed 0 to speed 15.
When S1=S2=S3=S4=OFF, the frequency input
manner is selected via code P00.06 or P00.07.
When all S1=S2=S3=S4 terminals aren’t off, it
runs at multi-step which takes precedence of
keypad, analog value, high-speed pulse, PLC,
communication frequency input. Select at most
16 stages speed via the combination code of
S1, S2, S3, and S4.
The start-up and stopping of multi-step running
is determined by function code P00.06, the
relationship between S1,S2,S3,S4 terminals and
multi-step speed is as following:
S1 OFF ON OFF ON OFF ON OFF ON
S2 OFF OFF ON ON OFF OFF ON ON
S3 OFF OFF OFF OFF ON ON ON ON
P10.03
The running
time of
stage 0
0.0s
○
P10.04
Multi-step
speed 1
0.0%
○
P10.05
The running
time of
stage 1
0.0s
○
P10.06
Multi-step
speed 2
0.0%
○
P10.07
The running
time of
stage 2
0.0s
○
P10.08
Multi-step
speed 3
0.0%
○
P10.09
The running
time of
stage 3
0.0s
○
P10.10
Multi-step
speed 4
0.0%
○
P10.11
The running
time of
stage 4
0.0s
○
P10.12
Multi-step
speed 5
0.0%
○
P10.13
The running
time of
stage 5
0.0s
○
P10.14
Multi-step
speed 6
0.0%
○
P10.15
The running
time of
stage 6
0.0s
○
P10.16
Multi-step
speed 7
0.0%
○
P10.17
The running
time of
stage 7
0.0s
○
P10.18
Multi-step
speed 8
0.0%
○
P10.19
The running
time of
stage 8
0.0s
○
P10.20
Multi-step
speed 9
0.0%
○