Astraada DRV-24 frequency inverters Function Parameters
45
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
2:AI2 setting voltage
3:AI3 setting voltage
4:HDI setting voltage
5:Multi-step speed setting voltage
;
6:PID setting voltage
;
7:MODBUS communication setting voltage
;
8~10: Reversed
Note: 100% corresponds to the rated voltage
of the motor.
P04.28
Keypad
setting
voltage
The function code is the voltage digital set
value when the voltage setting channel is
selected as “keypad selection”
The setting range:0.0%~100.0%
100.0%
○
P04.29
Voltage
increasing
time
Voltage increasing time is the time when the
inverter accelerates from the output minimum
voltage to the output maximum voltage.
Voltage decreasing time is the time when the
inverter decelerates from the output maximum
voltage to the output minimum voltage.
The setting range:0.0~3600.0s
5.0s
○
P04.30
Voltage
decreasing
time
5.0s
○
P04.31
Output
maximum
voltage
Set the upper and low limit of the output
voltage.
The setting range of P04.31:P04.32~100.0%
(the rated voltage of the motor)
The setting range of P04.32:0.0%~ P04.31
(the rated voltage of the motor)
100.0%
◎
P04.32
Output
minimum
voltage
0.0%
◎
P04.33
Weakenin
g
coefficient
in
constant
power
zone
Adjust the output voltage of the inverter in
SVPWM mode when weakening.
Note: Invalid in the constant torque mode.
The setting range of P04.33:1.00~1.30
1.00
○
P05 Group Input terminals
P05.00
HDI input
selection
0: HDI is high pulse input. See P05.49~P05.54
1:HDI is switch input
0
◎