Astraada DRV-24 frequency inverters Function Parameters
70
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
Setting range: 0.001~10.000s
P09.08
PID control
deviation
limit
The output of PID system is relative to the
maximum deviation of the close loop
reference. As shown in the diagram below, PID
adjustor stops to work during the deviation
limit. Set the function properly to adjust the
accuracy and stability of the system.
Setting range:0.0~100.0%
0.0%
○
P09.09
Output
upper limit
of PID
These parameters are used to set the upper
and lower limit of the PID adjustor output.
100.0 % corresponds to Max. Frequency or the
Max. Voltage of ( P04.31)
Setting range of P09.09: P09.10~100.0%
Setting range of P09.10: -100.0%~P09.09
100.0%
○
P09.10
Output
lower limit
of PID
0.0%
○
P09.11
Feedback
offline
detection
value
Set the PID feedback offline detection value,
when the detection value is smaller than or
equal to the feedback offline detection value,
and the lasting time exceeds the set value in
P09.12, the inverter will report “PID feedback
offline fault” and the keypad will display PIDE.
Setting range of P09.11: 0.0~100.0%
Setting range of P09.12: 0.0~3600.0s
0.0%
○
P09.12
Feedback
offline
detection
time
1.0s
○
P09.13
PID
adjustment
selection
0x00~0x11
LED ones:
0:Keep on integral adjustment when the
frequency achieves the upper and low limit;
the integration shows the change between the
reference and the feedback unless it reaches
the internal integral limit. When the trend
between the reference and the feedback
0x0001
○