Astraada DRV-24 frequency inverters Function Parameters
40
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
percentage
coefficient P
parameter of the current loop which affects
the dynamic response speed and control
accuracy directly. Generally, users do not need
to change the default value;
Only apply to the vector control mode without
PG 0 (P00.00=0).
Setting range:0~65535
P03.10
Current
loop
integral
coefficient I
1000
○
P03.11
Torque
setting
method
This parameter is used to enable the torque
control mode, and set the torque setting
means.
0:Torque control is invalid
1:Keypad setting torque(P03.12)
2:Analog AI1 setting torque
3:Analog AI2 setting torque
4:Analog AI3 setting torque
5:Pulse frequency HDI setting torque
6: Multi-step torque setting
7:MODBUS communication setting torque
8~10: Reserved
Note: Setting mode 2~7, 100% corresponds to
3 times of the motor rated current
0
○
P03.12
Keypad
setting
torque
Setting range: -300.0%~300.0%(motor rated
current)
50.0%
○
P03.13
Torque
given filter
time
0.000~10.000s
0.100s
○
P03.14
Setting
source of
forward
rotation
upper-limit
frequency
in torque
control
0:keypad setting upper-limit frequency(P03.16
sets P03.14, P03.17 sets P03.15)
1:Analog AI1 setting upper-limit frequency
2:Analog AI2 setting upper-limit frequency
3:Analog AI3 setting upper-limit frequency
4:Pulse frequency HDI setting upper-limit
frequency
5:Multi-step setting upper-limit frequency
6:MODBUS communication setting upper-limit
frequency
7~9: Reserved
Note: setting method 1~9, 100% corresponds
to the maximum frequency
0
○
P03.15
Setting
source of
reverse
rotation
upper-limit
frequency
in torque
control
0
○
P03.16
Torque
control
forward
rotation
This function is used to set the upper limit of
the frequency. P03.16 sets the value of P03.14;
P03.17 sets the value of P03.15.
Setting range:0.00 Hz~P00.03 (the Max. output
50.00
Hz
○