Astraada DRV-24 frequency inverters Function Parameters
56
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
sequence of
running
command
running command channels.
0:Keypad control→terminals control
→communication control
1:Keypad control←→terminals control
2:Keypad control←→communication control
3:Terminals control←→communication control
P07.04
STOP/RST
stop
function
Select the stop function by STOP/RST.
STOP/RST is effective in any state for the
keypad reset.
0:Only valid for the keypad control
1:Both valid for keypad and terminals control
2:Both valid for keypad and communication
control
3:Valid for all control modes
0
○
P07.05
Displayed
parameters
1 of running
state
0x0000~0xFFFF
BIT0:running frequency (Hz on)
BIT1:set frequency(Hz flickering)
BIT2:bus voltage (Hz on)
BIT3:output voltage(V on)
BIT4:output current(A on)
BIT5:running rotation speed (rpm on)
BIT6:output power(% on)
BIT7:output torque(% on)
BIT8:PID reference(% flickering)
BIT9:PID feedback value(% on)
BIT10:input terminals state
BIT11:output terminals state
BIT12:torque set value(% on)
BIT13:pulse counter value
BIT14:reserved
BIT15:PLC and the current step of multi-step
speed
0x03FF
○
P07.06
Displayed
parameters
2 of running
state
0x0000~0xFFFF
BIT0: analog AI1 value (V on)
BIT1: analog AI2 value (V on)
BIT2: analog AI3 value (V on)
BIT3: high speed pulse HDI frequency
BIT4: motor overload percentage (% on)
BIT5: the inverter overload percentage (% on)
BIT6: ramp frequency given value(Hz on)
BIT7: linear speed
BIT8: AC inlet current (A on)
BIT9~15:reserved
0x0000