Astraada DRV-24 frequency inverters Function Parameters
27
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
forward rotation, reverse rotation and forward
jogging and reverse jogging of the
multi-function terminals
2:Communication running command channel
(“LOCAL/REMOT” on);
The running command is controlled by the
upper monitor via communication
P00.03
Max. output
frequency
This parameter is used to set the maximum
output frequency of the inverter. Users need to
pay attention to this parameter because it is
the foundation of the frequency setting and the
speed of acceleration and deceleration.
Setting range: P00.04~400.00Hz
50.00H
z
◎
P00.04
Upper limit
of the
running
frequency
The upper limit of the running frequency is the
upper limit of the output frequency of the
inverter which is lower than or equal to the
maximum frequency.
Setting range:P00.05~P00.03 (Max. output
frequency)
50.00H
z
◎
P00.05
Lower limit
of the
running
frequency
The lower limit of the running frequency is that
of the output frequency of the inverter.
The inverter runs at the lower limit frequency if
the set frequency is lower than the lower limit.
Note: Max. output frequency ≥ Upper limit
frequency ≥ Lower limit frequency
Setting range:0.00Hz~P00.04 (Upper limit of
the running frequency)
0.00Hz
◎
P00.06
A frequency
command
selection
Note: A frequency and B frequency can not set
as the same frequency given method. The
frequency source can be set by P00.09.
0:Keypad data setting
Modify the value of function code P00.10 (set
the frequency by keypad) to modify the
frequency by the keypad.
1:Analog AI1 setting(corresponding keypad
potentiometer)
2:Analog AI2 setting(corresponding terminal
AI2)
3:Analog AI3 setting(corresponding terminal
AI3)
Set the frequency by analog input terminals.
Astraada DRV-24 series inverters provide 3
channels analog input terminals as the
standard configuration, of which AI1 is
adjusting through analog potentiometer, while
AI2 is the voltage/current option
(0~10V/0~20mA) which can be shifted by
jumpers; while AI3 is voltage input
(-10V~+10V).
0
○
P00.07
B frequency
command
selection
2
○