Astraada DRV-24 frequency inverters Function Parameters
57
Functio
n code
Name
Detailed instruction of parameters
Defaul
t value
Modify
P07.07
The
parameter
selection of
the stop
state
0x0000~0xFFFF
BIT0:set frequency(Hz on, frequency flickering
slowly)
BIT1:bus voltage (V on)
BIT2:input terminals state
BIT3:output terminals state
BIT4:PID reference (% flickering)
BIT5:PID feedback value(% flickering)
BIT6:torque reference(% flickering)
BIT7:analog AI1 value(V on)
BIT8:analog AI2 value(V on)
BIT9: analog AI3 value(V on)
BIT10:high speed pulse HDI frequency
BIT11:PLC and the current step of multi-step
speed
BIT12:pulse counters
BIT13~BIT15:reserved
0x00FF
○
P07.08
Frequency
display
coefficient
0.01~10.00
Displayed frequency=running frequency*
P07.08
1.00
○
P07.09
Speed
display
coefficient
0.1~999.9%
Mechanical rotation speed =120*displayed
running frequency×P07.09/motor pole pairs
100.0%
○
P07.10
Linear
speed
displayed
coefficient
0.1~999.9%
Linear speed= Mechanical rotation
speed×P07.10
1.0%
○
P07.11
Rectifier
bridge
module
temperatur
e
-20.0~120.0°C
●
P07.12
Converterin
g module
temperatur
e
-20.0~120.0°C
●
P07.13
Software
version
1.00~655.35
●
P07.14
Local
accumulativ
e running
time
0~65535h
●
P07.15
High bit of
power
consumptio
n
Display the power used by the inverter.
The power consumption of the inverter
=P07.15*1000+P07.16
Setting range of P07.15: 0~65535 kWh(*1000)
●