Asentria SiteBoss 530 User Manual
105
Event Sensor Reporting Enabled
is an ON/OFF toggle to enable the Event Sensor Reporting feature. See the
Event Sensor Reporting section in the Features chapter for more information.
Clear Settings for This EventSensor
when selected will immediately clear all of the configured settings for this
sensor and remove it from the Sensor Events menu (except for Internal Sensors). If "Confirmation Prompt“ in General
Settings is ON, then there will be a confirmation prompt (
Are you sure (y/n)?
) displayed before clearing the
configured settings. Return to the Sensor Events menu to assign it a new slot, if desired, and reconfigure it.
Analog Input n
SiteBoss 530 External Analog Input Event 1
Device Number: 5 Device ID: 20020000 Device Name: unnamed
A) Analog Input Enabled [OFF]
B) Name [unnamed]
C) Input Polarity [POSITIVE]
D) Deadband [30]
E) Very High Event Settings [600] [] [140] [Info]
F) High Event Settings [600] [] [140] [Info]
G) Return to Normal Settings [-] [] [140] [Info]
H) Low Event Settings [0] [] [140] [Info]
I) Very Low Event Settings [0] [] [140] [Info]
J) Unit Conversion Settings []
Analog Input Enabled
is an ON/OFF toggle to enable this analog sensor.
Name
sets the name to be given to this input point. Default setting is unnamed.
Input Polarity
indicates to the unit whether the input polarity will be positive or negative.
Deadband
is the range on either side of a voltage setting that prevents the alarm from repeatedly going in and out off
the "alarm state" as the actual voltage fluctuates above and below the voltage setting.
Very High / High / Low / Very Low Event Settings
displays a menu where the voltage at each level can be
configured to alarm along with the action(s) to occur, trap number, and class. In the case of Very High or High levels,
the alarm will occur as the voltage rises above the setting. In the case of Low or Very Low, the alarm will occur as the
voltage drops below the setting.
displays a menu where the optional action definition for alarms as they return to a normal
state can be configured.
displays a menu where “real world” values can be configured.
Very High / High / Low / Very Low Analog Input Event Settings
SiteBoss 530 External Analog Input Event Settings
Device Number: 5 Device ID: 20020000 Device Name: Test unnamed
A) Very High Event Value [750]
B) Very High Event Actions []
C) Very High Event Trap Number [140]
D) Very High Event Class [Info]
The menu for setting Very High Event Value settings is shown. Menus for High/Low/Very Low are identical.
Very High Event Value
sets the voltage (in tenths) at which the Very High Event Actions will be triggered.
Very High Event Actions
displays the Actions List, a menu where the action string for the event is configured. This
field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to the
for more information.