134
SV200 DC Hardware Manual
920-0126A
4/14/2017
P-69 (BD)
Brake disengage Delay
Data Range
Default
Unit
LED Display
0 - 32000
200
ms
200
P-70 (BE)
Brake engage delay
Data Range
Default
Unit
LED Display
0 - 32000
200
ms
200
BD only takes effect if the BO command is set to 1 or 2. After a drive is enabled this is the time value a move may be delayed waiting
for the brake to disengage. When beginning a move the delay value must expire before a move can take place. The delay timer begins
counting down immediately after the drive is enabled and the brake output is set. The delay is set in milliseconds.
BE only takes effect if the BO command is set to 1 or 2. After a drive is commanded to be disabled this is the time value the actual
disabling of the drive output is delayed. When using the dedicated brake output (see BO command), the output is activated immediately
with the disable command, then the drive waits the delay time before turning off the motor current.
S_ON Signal
OFF
ON
Motor ON
OFF
ON
Brake Action
OFF
ON
Brake Signal
OFF
ON
Motion Command
OFF
ON
Actual Motion
OFF
ON
Brake disengage
delay P-69
Brake engage
delay P-70
P-71 (FI)
Input X9 noise filter
Data Range
Default
Unit
LED Display
0 - 32767
0
---
0
Applies a digital filter to the input X9. The digital input must be at the same level for the time period specified by the FI command
before the input state is updated. For example, if the time value is set to 100 the input must remain high for 100 processor cycles
before high is updated as the input state. One processor cycle is 250µsec. A value of “0” disables the filter.
P-72 (FI)
Input X10 noise filter
Data Range
Default
Unit
LED Display
0 - 32767
0
---
0
Applies a digital filter to the input X10. The digital input must be at the same level for the time period specified by the FI command
before the input state is updated. For example, if the time value is set to 100 the input must remain high for 100 processor cycles
before high is updated as the input state. One processor cycle is 250µsec. A value of “0” disables the filter.
P-73 (FI)
Input X11 noise filter
Data Range
Default
Unit
LED Display
0 - 32767
0
---
0
Applies a digital filter to the input X11. The digital input must be at the same level for the time period specified by the FI command
before the input state is updated. For example, if the time value is set to 100 the input must remain high for 100 processor cycles
before high is updated as the input state. One processor cycle is 250µsec. A value of “0” disables the filter.