P-61 (FA)
Analog X1, X2 function
Data Range
Default
Unit
LED Display
11 - 33
33
---
33
Defines the function of analog inputs X1 and X2, by two digits, from right to left.
Digit 1: Input X1 function
Digit 2: Input X2 function
Input X1:
1: Analog input X1 is used as velocity or position reference input.
2: Not used.
3: Analog input X1 is used as general purpose analog input.
Input X2:
1: Not used.
2: Analog input X2 is used as torque reference input.
3: Analog input X2 is used as general purpose analog input.
In SVX Servo Suite Parameter Table tab, 2 commands are llisted: FA1 represents the first digit (X1), and FA2 represents the second
digit (from right to left).
P-62 (SI)
Servo enable input setting
Data Range
Default
Unit
LED Display
1, 2, 3
2
---
2
Input X3 is the default enable input on all drives. There are 3 possible usage states for the Enable function:
SI1: Drive is enabled when X3 is open.
SI2: Drive is enabled when X3 is closed.
SI3: Input X3 is used as a general purpose input.
Refer to Section 7.1.1 Drive Servo On Settings.
P-63 (AI)
Alarm Reset input setting
Data Range
Default
Unit
LED Display
1, 2, 3
1
---
1
Defines the function of the X4 input. This input can be used to clear a drive fault and reset the Alarm Code (see AL command).
Refer to Section 7.1.2 Alarm Reset.