You are prompted to enter the Alarm 8 set point value:
Alarm #8=xx.x % CH4
New Value?
7. Enter the Alarm 8 set point value. Note that methane alarms are al-
ways high alarms. So, for example, Alarm 7 could be a high alarm, and
Alarm 8 high/high.
8. Press
Cancel
or
Enter
to exit this menu option.
Alarm Configure
Define whether alarms should trigger based on a high alarm or a low
alarm condition. If you have the combustibles or methane options, Alarms
5 through 8 always act as high alarms. So, for example, Alarm 5 could be a
high combustibles alarm, and Alarm 6 could be a high/high combustibles
alarm.
Whether Alarm 3 is set high or low only applies if it is set to track
oxygen levels (% O
2
). If Alarm 3 is set to trigger at the start of a cali-
bration or verification, this option does not apply.
Configuring the alarms
1. From the
Alarm
menu, select
Alarm Configure
.
2. Define Alarm 3 and Alarm 4 as high or low alarms.
3. Press
Cancel
to exit this menu option.
Relay Configure
All Series 2000 control unit relays are Form A, normally open contacts.
You can use the software to set whether these alarms should close on
an alarm condition (energize on alarm) or open on an alarm condition
(de-energize on alarm). This menu option applies to all alarms except for
the service and watchdog alarms, which are always set to de-energize on
alarm (fail-safe).
NOTE
Summary of Contents for Thermox Series 2000 WDG-IV
Page 14: ...xiv Thermox Series 2000 WDG IV IVC IVCM This page intentionally left blank ...
Page 32: ...2 8 Thermox Series 2000 WDG IV IVC IVCM This page intentionally left blank ...
Page 59: ...Installation 3 27 Figure 3 20 Sensor connections with all sensor options ...
Page 67: ...Installation 3 35 Figure 3 24 Series 2000 2 wire RS 485 communication connections ...
Page 69: ...Installation 3 37 Figure 3 25 Series 2000 4 wire RS 485 communication connections ...
Page 72: ...3 40 Thermox Series 2000 WDG IV IVC IVCM This page intentionally left blank ...
Page 100: ...4 28 Thermox Series 2000 WDG IV IVC IVCM This page intentionally left blank ...
Page 126: ...5 26 Thermox Series 2000 WDG IV IVC IVCM This page intentionally left blank ...
Page 143: ...Service and Parts 7 3 Figure 7 1 Wiring diagram for standard sensor ...
Page 145: ...Service and Parts 7 5 Figure 7 2 Cell replacement ...
Page 155: ...7 15 Thermox Series 2000 WDG IV IVC IVCM This page intentionally left blank ...
Page 181: ...A 26 Thermox Series 2000 WDG IV I VC IVCM This page intentionally left blank ...
Page 185: ...B 4 Thermox Series 2000 WDG IV IVC IVCM This page intentionally left blank ...
Page 191: ...D 2 Thermox Series 2000 WDG IV IVC IVCM This page intentionally left blank ...