31.9 The BASE SPARK NUMBER defines the spark number which will be used when
no overriding conditions are active. The selectable range for the base spark
number is 1 to 8.
FROM
PRESS
MAN
TO ADJUST
TO ADVANCE
TO GO BACK
THE VALUE
TO THE NEXT
TO THE
MENU
HOME
SCREEN
ESC
31.10 The MISC-IN SPARK NUMBER defines the spark selection number to be
utilized when the Aux. Misc. Input is activated (connected to ground). The
selectable range for Misc-in Spk Number is 0-8. When set to zero, this feature
is disabled and will not override the active spark number.
TO ADJUST
TO ADVANCE
TO GO BACK
THE VALUE
TO THE NEXT
TO THE
MENU
HOME
SCREEN
ESC
NOTE: Spark number selection criteria
in order of priority:
1. Misc-In
2. High EAVG
3. High single cylinder COV
4. 4-20mA Current Loop
5. Base Spark Number
NOTE: If the spark number used is
changed through a Modbus key com-
mand message, that spark will be used
until another condition changes (ex:
EAVG was active, and no longer is, or
the 4-20mA current loop changes).
⬆
⬇
NEXT
⬆
⬇
NEXT