This indicates that the voltage
supplied to the right Output Module
(rails 3 and 4) has deviated outside
of the normal operating range. This
can result from poor wiring, an
inadequate power supply, or a
discharged/weak supply battery.
This screen indicates a problem with
the diagnostic detection circuit on
rails 1 and 3.
25.7 After all of the diagnostics have been read, the user can reset the warnings and
faults by pressing the reset key from the
HOME SCREEN
as pictured below.
PRESS
OR PRESS
THEN
TO EXIT
TO GO TO
PRESS
HOME
ESC
SCREEN
NEXT
Pressing the reset key performs all of the following actions:
n
Clears all diagnostic warnings from memory.
n
Clears all diagnostic faults from memory.
n
Clears a latched shutdown condition when the input is no longer grounded.
n
Causes temporary cylinder timing offsets to be overwritten from
EEPROM
memory.
n
Resets internal communication statistics.
RESET