14-4
TROUBLESHOOTING
SM DLF 1-A.1 GB
No
Problem
AO
5
4
3
2
1
28
Model A
No
1
1
1
0
0
29
Model B
No
1
1
1
0
1
30
Model C
No
1
1
1
1
0
31
Model D
No
1
1
1
1
1
*
CN / LSN Units only
14.3.2
Indoor Unit Diagnostics and Corrective Actions
No.
Fault
Probable Cause
Corrective Action
1
Sensor failures
of all types
Check sensor connections or
replace sensor
2
Communication
mismatch
Indoor and Outdoor
controllers are with
different versions
Replace Indoor controller
3
No
Communication
Communication or
grounding wiring is not
good.
Check Indoor to Outdoor
wiring and grounding
4
No Encoder
Indoor electronics or
motor
Check motor wiring, if ok,
replace motor, if still not ok,
replace Indoor controller.
5
Outdoor Unit
Fault
Outdoor controller
problem
Switch to Outdoor
diagnostics.
6
EEPROM Not
Updated
System is using ROM
parameters and not
EEPROM parameters
No action, unless special
parameters are required for
unit operation.
7
Bad EEPROM
No action, unless special
parameters are required for
unit operation.
8
Bad
Communication
Communication quality
is low reliability
Check Indoor to Outdoor
wiring and grounding
9
Using EEPROM
data
No problem. System is
using EEPRRRROM
parameters
14.3.3
Outdoor Unit Diagnostics
The outdoor alarm outputs are defined in the following way
:
No
Problem
AO
5
4
3
2
1
1
OCT is disconnected
Yes
0
0
0
0
1
2
OCT is shorted
Yes
0
0
0
1
0
3
CTT is disconnected
Yes
0
0
0
1
1
4
CTT is shorted
Yes
0
0
1
0
0
5
HST is disconnected (when enabled)
Yes
0
0
1
0
1
6
HST is shorted (when enabled)
Yes
0
0
1
1
0
7
OAT is disconnected (when enabled)
Yes
0
0
1
1
1
8
OAT is shorted (when enabled)
Yes
0
1
0
0
0
9
OMT is disconnected (DCI72 / 72Z / 80)
Yes
0
1
0
0
1
Summary of Contents for Multi Split DUO 50 DCI
Page 14: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit DCI 25 35 50 4 3 Outdoor Unit DCI 60...
Page 15: ...4 3 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 4 Outdoor Unit DCI 72Z...
Page 48: ...7 5 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 72Z Cooling DCI 72Z Heating...
Page 96: ...15 8 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 8 Outdoor Unit DCI 50...
Page 98: ...15 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 10 Outdoor Unit DCI 60...
Page 100: ...15 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 12 Outdoor Unit DCI 72Z...