13-4
CONTROL SYSTEM
SM DLF 1-A.1 GB
13.1.6
Minimum On and Off Time
3 minutes
13.1.7 Indoor
Fan
Control
8 Indoor fan speeds are determined for each model. 4 speeds for cool/dry/fan modes and 4speeds
for heat mode.
When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate constantly
at set speed.
When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set
according to the cool/heat load.
13.1.7.1 Turbo
Speed
The Turbo speed is activated during the first 30 minutes of unit operation when auto fan speed is
selected and under the following conditions:
Difference between set point and actual room temperature is bigger then 3 degrees.
Room temperature > 22 for cooling, or < 25 for heating.
13.1.8 Outdoor
Fan
Control
13.1.8.1
Outdoor Fan Control for DCI25/35/50/60
7 outdoor fan speeds are determined for each model. 3 speeds for cool and dry modes, and 3speeds
for heat mode, and a very low speed.
Outdoor fan speed is a function of compressor frequency and outdoor air temperature (OAT).
4 routines for fan control are determined. The control routine selection depends on operation mode,
compressor speed, outdoor air temperature (OAT) and heat sink temperature (HST).
Routine Conditions
A
Heating with OAT < 15
ഒ
or
Cooling with OAT > 20
ഒ
, or Faulty OAT
B
Cooling with 20
ഒ
> OAT > 7
ഒ
C
Cooling with 7
ഒ
> OAT
D
Heating with OAT > 15
ഒ
OFAN Speed
Compressor
Target Frequency
Routin
A
Routin
B
Routin
C
Routin
D
Freq=0
OFF
OFF
OFF
OFF
10 ≤ Freq <
OFLowFreq
Low
Low
VL
Low
OFLowFreq
≤ Freq<
OFMedFreq
Medium
Low
VL
Low
OFMedFreq≤ Freq
High
Low
Low
Medium
Summary of Contents for Multi Split DUO 50 DCI
Page 14: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit DCI 25 35 50 4 3 Outdoor Unit DCI 60...
Page 15: ...4 3 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 4 Outdoor Unit DCI 72Z...
Page 48: ...7 5 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 72Z Cooling DCI 72Z Heating...
Page 96: ...15 8 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 8 Outdoor Unit DCI 50...
Page 98: ...15 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 10 Outdoor Unit DCI 60...
Page 100: ...15 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 12 Outdoor Unit DCI 72Z...