PIPE CONECTIONS TO THE UNIT
Connecting to the indoor unit
1. Align the center of the pipes and
finger tight the flare nut.
2. Use the torque wrench to tighten
the nut firmly.
Connecting to the outdoor unit
1. Align the center of the pipes to the
valves.
2. Use the torque wrench to tighten
the valves firmly according to table:
Tube (Inch)/
Torque(N.m)
1/4 3/8 1/2 5/8 3/4
Flare Nuts
13-18 40-45 60-65 70-75 80-85
Valve Cap
13-20 13-20 18-25 18-25 40-50
Service Port
Cap
11-13 11-13 11-13 11-13 11-13
EVACUATION OF PIPES AND INDOOR UNIT
After connection the unions of the indoor and
outdoor units, evacuate the air from the tubes
and from the indoor unit as follows:
1. Connect the charging hoses with a push pin
to the low and high sides of the charging set
and the service port of the suction and liquid
valves. Be sure to connect the end of the
charging hose with the push pin to the service
port.
2. Connect the center hose of the charging set
to a vacuum pump.
3. Turn on the power switch of the vacuum
pump and make sure that the needle in the
gauge moves from 0MPa (0cm Hg)
to - 0.1 Mpa (-76cm Hg). Let the pump run for
fifteen minutes.
4. Close the valves of both the low and high
sides of the charging set and turn off the
vacuum pump. Note that the needle in the
gauge should not move after approximately
five minutes.
5. Disconnect the charging hose from the
vacuum pump and from the service ports of
the suction and liquid valves.
6. Tighten the service port caps from both
valves, and open them using a hexagonal
Allen wrench.
7. Remove the valve caps from both valves, and
open them using a hexagonal Allen wrench.
8. Remount valve caps onto both of the valves.
9. Check for gas leaks from the four unions and
from the valve caps.
Test with electronic leak detector or with a
sponge immersed in soapy water for bubbles.
NOTE: For additional charge of various tubing
lengths, refer to outdoor unit table.
Summary of Contents for Multi Split DUO 50 DCI
Page 14: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit DCI 25 35 50 4 3 Outdoor Unit DCI 60...
Page 15: ...4 3 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 4 Outdoor Unit DCI 72Z...
Page 48: ...7 5 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 72Z Cooling DCI 72Z Heating...
Page 96: ...15 8 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 8 Outdoor Unit DCI 50...
Page 98: ...15 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 10 Outdoor Unit DCI 60...
Page 100: ...15 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 12 Outdoor Unit DCI 72Z...