5-21
PERFORMANCE DATA & PRESSURE CURVES
SM DLF 1-A.1 GB
5.5
DLF 72 / DCI 72Z
5.5.1 Cooling
Capacity
(kW)
ID COIL ENTERING AIR DB/WB TEMPERATURE [C0]
OD COIL ENTERING AIR
DB TEMPERATURE [C0]
DATA
22/15
24/17
27/19
29/21
32/23
-10 - 20 (protec-
tion range)
TC
80 - 110 % of nominal
SC
80 - 105 % of nominal
PI
25 - 50 % of nominal
25
TC
6.77
7.21
7.65
8.09
8.54
SC
5.51
5.63
5.74
5.85
5.96
PI
1.61
1.64
1.67
1.70
1.73
30
TC
6.44
6.88
7.33
7.77
8.21
SC
5.37
5.49
5.60
5.71
5.82
PI
1.80
1.83
1.86
1.89
1.92
35
TC
6.12
6.56
7.00
7.44
7.88
SC
5.24
5.35
5.46
5.57
5.68
PI
1.99
2.02
2.05
2.08
2.11
40
TC
5.79
6.23
6.67
7.12
7.56
SC
5.10
5.21
5.32
5.43
5.55
PI
2.18
2.21
2.24
2.27
2.30
46
TC
5.40
5.84
6.28
6.73
7.17
SC
4.93
5.04
5.15
5.27
5.38
PI
2.40
2.43
2.46
2.50
2.53
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
5.5.2
Capacity Correction Factors (Cooling)
Cooling Capacity Ratio Vs.Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
20
25
30
35
40
45
Outdoor Temperature DB [deg C]
Capacity Factor
Summary of Contents for Multi Split DUO 50 DCI
Page 14: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit DCI 25 35 50 4 3 Outdoor Unit DCI 60...
Page 15: ...4 3 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 4 Outdoor Unit DCI 72Z...
Page 48: ...7 5 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 72Z Cooling DCI 72Z Heating...
Page 96: ...15 8 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 8 Outdoor Unit DCI 50...
Page 98: ...15 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 10 Outdoor Unit DCI 60...
Page 100: ...15 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 12 Outdoor Unit DCI 72Z...