13-19
CONTROL SYSTEM
SM DLF 1-A.1 GB
13.1.25 Outdoor
Unit
Controller
13.1.25.1 Outdoor Unit Controller - Jumper setting
JP9 Jumper Layout
Reserved
(PIN 9)
ODU3
(PIN 7)
ODU2
(PIN 5)
ODU1
(PIN 3)
ODU0
(PIN 1)
GND
(PIN 10)
GND
(PIN 8)
GND
(PIN 6)
GND
(PIN 4)
GND
(PIN 2)
13.1.26 ODU
Model
Selection
ODU3
ODU2
ODU1
ODU0
ODU Model
OFF
OFF
OFF
ON
A (Single DCI 25)
OFF
OFF
ON
OFF
B (Single DCI 35)
OFF
OFF
ON (PIN3 & PIN4)
ON (PIN1 & PIN2)
C (Single DCI 50)
OFF
ON (PIN5 & PIN6)
OFF
OFF
D (Single DCI 60)
ON (PIN7 & PIN8)
ON (PIN5 & PIN6)
OFF
OFF
L (Single DCI 72Z)
13.1.27
Outdoor Unit Controller
13.1.27.1 Outdoor Unit Controller - DIP Switch setting
ODU3
ODU2
ODU1
ODU0
ODU MODEL
OFF
OFF
OFF
ON
DCI 25
OFF
OFF
ON
OFF
DCI 35
OFF
OFF
ON
ON
DCI 50
OFF
ON
OFF
OFF
DCI 60
ON
ON
OFF
OFF
DCI 72Z
13.2 Test
Mode
13.2.1 Entering
Test
Mode
System can enter Test mode in two ways:
Automatically when the following conditions exists for 30 minutes continuously:
Mode = Cool, Set point = 16, Room temperature = 27(+1/-2), Outdoor temperature = 35(+2/-1)
Or
Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature = 7±(+1/-2)
Manually when entering diagnostics with the following settings:
Mode = Cool, Set point = 16
Mode = Heat, Set point = 30
ON
1
2
3
4
5
6
DIP
ODU0
ODU1
ODU2
ODU3
N.A.
N.A.
ODU MODEL SETTING
Summary of Contents for Multi Split DUO 50 DCI
Page 14: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit DCI 25 35 50 4 3 Outdoor Unit DCI 60...
Page 15: ...4 3 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 4 Outdoor Unit DCI 72Z...
Page 48: ...7 5 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 72Z Cooling DCI 72Z Heating...
Page 96: ...15 8 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 8 Outdoor Unit DCI 50...
Page 98: ...15 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 10 Outdoor Unit DCI 60...
Page 100: ...15 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 12 Outdoor Unit DCI 72Z...