5-7
PERFORMANCE DATA & PRESSURE CURVES
SM DLF 1-A.1 GB
5.2.3 Heating
ID COIL ENTERING AIR DB TEMPERATURE [°C]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [°C]
DATA
15
20
25
-15/-16
TC
2.67
2.49
2.30
PI
0.70
0.77
0.84
-10/-12
TC
2.98
2.79
2.60
PI
0.84
0.91
0.98
-7/-8
TC
3.20
3.02
2.83
PI
0.95
1.02
1.09
-1/-2
TC
3.32
3.13
2.94
PI
1.00
1.07
1.14
2/1
TC
3.39
3.20
3.02
PI
1.04
1.11
1.18
7/6
TC
4.39
4.20
4.01
PI
1.09
1.16
1.23
10/9
TC
4.63
4.44
4.26
PI
1.15
1.23
1.30
15/12
TC
4.87
4.68
4.50
PI
1.22
1.29
1.36
15-24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
LEGEND
TH –
Total Heating Capacity, kW
PI
– Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
5.2.4
Capacity Correction Factors (Heating)
Heating Capacity Ratio Vs. Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
-20
-15
-10
-5
0
5
10
15
Outdoor WB Temperature [deg C]
Capacity Factor
Summary of Contents for Multi Split DUO 50 DCI
Page 14: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit DCI 25 35 50 4 3 Outdoor Unit DCI 60...
Page 15: ...4 3 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 4 Outdoor Unit DCI 72Z...
Page 48: ...7 5 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 72Z Cooling DCI 72Z Heating...
Page 96: ...15 8 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 8 Outdoor Unit DCI 50...
Page 98: ...15 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 10 Outdoor Unit DCI 60...
Page 100: ...15 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 12 Outdoor Unit DCI 72Z...