8-1
ELECTRICAL DATA
SM DLF 1-A.1 GB
8.
ELECTRICAL DATA
8.1 Single
Phase
Units
MODEL
DLF 25-35
DLF 50-60
DLF 72
Power Supply
To Indoor
To Indoor or Outdoor
To Outdoor
1PH – 230V – 50 Hz
1PH – 230V – 50 Hz
1PH – 230V – 50 Hz
Max Current, A
10.5
15
15
Circuit Breaker
16
20
20
Power Supply Wiring No. X
Cross Section mm
2
3 X 1.5 mm
2
3 X 2.5 mm
2
3 X 2.5 mm
2
Interconnecting Cable RC
Model No. X Cross Section
mm
2
4 X 1.5 mm
2
4 X 2.5 mm
2
4 X 2.5 mm
2