13-1
CONTROL SYSTEM
SM DLF 1-A.1 GB
13. CONTROL
SYSTEM
13.1
General Functions and Operating RulesThe DCI software is fully
parametric.
All the model dependent parameters are shown in Blue color and with Italic style [
parameter
].
The parameters values are given in the last section of this control logic chapter of the service man-
ual.
13.1.1 System
Operation
Concept
The control function is divided between indoor and outdoor unit controllers. Indoor unit is the system
‘Master’, requesting the outdoor unit for cooling/heating capacity supply. The outdoor unit is the
system ‘Slave’ and it must supply the required capacity unless it enters into a protection mode
avoiding it from supplying the requested capacity.
The capacity request is transferred via indoor to outdoor communication, and is represented by a
parameter called ‘NLOAD’. NLOAD is an integer number with values between 0 and 127, and it
represents the heat or cool load felt by the indoor unit.
13.1.2
Compressor Frequency Control
13.1.2.1 NLOAD
setting
The NLOAD setting is done by the indoor unit controller, based on a PI control scheme.
The actual NLOAD to be sent to the outdoor unit controller is based on the preliminary LOAD
calculation, the indoor fan speed, and the power shedding function.
NLOAD limits as a function of indoor fan speed:
Indoor Fan Speed Maximum NLOAD Cooling Maximum NLOAD Heating
Indoor Fan Speed
Maximum NLOAD Cooling
Maximum NLOAD Heating
Low
MaxNLOADIF1C
MaxNLOADIF1H
Medium
MaxNLOADIF2C
MaxNLOADIF2H
High
MaxNLOADIF3C
MaxNLOADIF3H
Turbo
MaxNLOADIF4C
MaxNLOADIF4H
Auto
MaxNLOADIF5C
MaxNLOADIF5H
NLOAD limits as a function of power shedding:
Mode
Power Shedding OFF
Power Shedding ON
Cooling
No limit
Nominal Cooling
Heating
No limit
Nominal heating
13.1.3
Target Frequency Setting
13.1.3.1
Target Frequency Setting for DCI 25/35/50/60/72Z
The compressor target frequency is a function of the NLOAD number sent from the indoor controller
and the outdoor air temperature.
Basic Target Frequency Setting:
Up
to
SW
35V12
NLOAD
Target Frequency [Hz]
<10
0
10
MinFreqC
in cool OR
MinFreqH
in heat mode
11-126
NLOAD (as long it is in the allowed range, if not, the
MinFreqC
or
Max FreqC
in
cool mode OR
MinFreqH
or
MaxFreqH
in heat mode will be selected).
127
MaxFreqC
in cool OR
MaxFreqH
in heat mode.
Summary of Contents for Multi Split DUO 50 DCI
Page 14: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit DCI 25 35 50 4 3 Outdoor Unit DCI 60...
Page 15: ...4 3 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 4 Outdoor Unit DCI 72Z...
Page 48: ...7 5 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 72Z Cooling DCI 72Z Heating...
Page 96: ...15 8 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 8 Outdoor Unit DCI 50...
Page 98: ...15 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 10 Outdoor Unit DCI 60...
Page 100: ...15 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 12 Outdoor Unit DCI 72Z...