4.3.1.3.1 Search All PLU
This is the main procedure to follow when installing a new installation or adding a luminaire(s) to the installation.
The display first shows the address ranges as it searches for each PLU installed on the signalling line as
follows:
[SEARCH PLUs] 0 Found
Searching 1000000 - 1000001
When all Luminaires / I/O Modules have been located, the display shows the number of devices found along
with a list of the serial numbers (in ascending numerical order) and, if already configured, the soft address
assigned.
[SEARCH PLUs] 89 Found
Serial No Address Entry
226492423 .
0
0001
226492423 0 0002
226492423 23 0003
226492423 10 DOUBLE ADDRESS 0004
Press the
buttons to scroll through the list and use the
number
buttons to configure the required soft
address to a PLU currently unassigned. Press the
✔
button to jump to the next PLU Serial number with an
unassigned soft address (address 000 or address 200). Press
Esc
to abort the search and list the serial
numbers found at that point.
Note: It is not normally possible for two serial numbers to be assigned to the same soft address. If a serial
number is changed to a soft address that is currently assigned to another luminaire, then the panel
automatically sets the other luminaire to address 000. This serial number will now also require re-assignment.
In the above example, however, the panel has found two serial numbers with the same soft address. The most
likely cause for this occurrence is that a new luminaire / I/O module has been added to this loop where the PLU
had been previously assigned to a soft address elsewhere. Adjust the soft addresses accordingly as described
above.
When adding a luminaire / I/O Module to a current installation, press the
button to highlight the serial number
field and use the
number
buttons to enter the serial number of the newly installed device. The display will
automatically jump to the required entry.
After any changes have been made, the display prompts for an AUTO-LEARN to be performed. This is an
essential procedure to update the panel's configuration memory with the changes.
4.3.1.3.2 Assign From Panel Configuration Memory
If a PC configuration file has been transmitted to and stored in the panel's memory, this function will
automatically assign soft addresses in each PLU in accordance with the configuration file data.
The display shows the progress of this procedure with the following display.
WORKING... 001 > 226492433
Each soft address is shown in turn along with the serial number of the device. When all devices have been
addressed, the display reverts to the main loops menu.
Perform an Auto-Learn following this procedure.