[TEST GROUP 1] <More
Lp:Adrs Duration Date Time
1:011 1 mins 11 FEB 2004 14:26
1:012 5 mins 11 FEB 2004 14:26
1:026 1 mins 11 FEB 2004 14:26
1:045 2 mins 11 FEB 2004 14:26
Press the
button to view the duration from the start of the test at which the failure was detected and the date
and time that the tests started.
3.2.5.1.2 Test
– Lights (Individually)
An individual luminaire can be tested. For example, this provides a convenient method to test a luminaire after
the tube has been replaced. The results for the individual test on this luminaire will be updated in the records
and can be viewed later using the test group option if required.
Highlight the INDIVIDUAL option and then press the
✔
button to select.
The display prompts for entry of the address of the device and the test duration as follows.
[INDIVIDUAL LIGHT TEST]
Loop Address Duration(minutes)
....
(Key in number then press
✔
)
Use the number buttons to enter the required loop number (1-4), on which the luminaire is wired, and then press
the
✔
button. The highlighted field automatically steps on to the address field. Enter the address of the
luminaire and then press the
✔
button. The highlighted field automatically steps on to the duration field. Enter
the duration required and then press the
✔
button. The test will begin and the display shows the following.
[INDIVIDUAL LIGHT TEST]
Loop Address Duration(minutes)
1 8 5
Testing. Light Output = 93
(Press Esc to Abort. 153s to finish)
The display indicates the measured light level output from the luminaire. On the bottom line, the time remaining
for the test is shown. At the end of the test, the display will indicate whether the test was passed or failed as
follows.
[INDIVIDUAL LIGHT TEST]
Loop Address Duration(minutes)
1 8 5
... ... ... ...
PASS
... ... ... ... ...
Press the
Esc
button to return to the test menu.