23
Enter the password using the number buttons and then press the
✔
button. As each number is entered, an
asterisk (*) is shown on the display. For example:
[ CONTROLS DISABLED ]
Please Enter Your Password
**
If the password is correct, the Level 2 Menu options will be shown.
If the password is incorrect, the display briefly shows the following message.
[ CONTROLS DISABLED ]
Please Enter Your Password
Password Not Recognised !
If at Level 1, on the press of any of the control buttons (Reset, User Function), the display automatically prompts
for the password. Enter the password as above (The function of the control button pressed is not initiated. The
button must be pressed again for the panel to action the required function).
3.2.1.2 Changing from Access Level 2 to 1
If the panel has an access key switch fitted, use the key switch.
Alternatively, if passwords are used, select the “Lock Controls” option – see section 3.2.9 for details.
3.2.2
Fault Condition
When the system registers a fault condition the display shows the cause of the fault in more detail.
An example of the display is shown below:
ZONE 0003 DEVICE MISSING
LOWER FLOOR
CORRIDOR A (NON-MAINT )
< Location Text for First Zone
< Location Text and Type of Device
1 Zone In Fault More>
< No. of Zones in FAULT
If more than one fault condition occurs, these will be shown on the display.
When the fault condition is corrected, the panel automatically clears the appropriate fault Status Indicators and
Display information.
Press the ‘
MUTE
’ button to acknowledge the fault. The display then shows the current time and date and
service centre telephone number along with the indication of the fault.
FOR SERVICE CALL
01234 567890
16:05
04 MAR 2002
< Panel access level
< Service Call Number
< and Time / Date
1 Zone In Fault More>
< No. of Zones in FAULT
To obtain more detailed information about the faults, press the
button. The display then presents a list of all
of the zones in a fault condition with the first fault highlighted. For example:
[ 2 Zones in Fault] More>
ZONE LOCATION
0003 LOWER FLOOR
0200 RECEPTION
< Zone #, Location Text and
< number of faults in each zone