27
3.2.5.1 Test
– Lights
The luminaires can be tested manually in their groups or individually.
[TEST LIGHTS]
GROUP
INDIVIDUAL
Highlight the required option and press the
✔
button to select.
3.2.5.1.1 Test
– Lights (By Group)
Select the Group option and the display shows the status of any completed tests and any tests currently in
progress. For example, the following shows the last test times and results for Groups 1 to 4.
[LIGHTING TEST GROUPS] More>
Group Period Date Time Result
.
1
.. 5 mins 01/12/03 12:00
✔
2 30 mins 02/11/03 15:30
✔
3 30 mins 02/10/03 08:30
✔
4 5 mins 03/11/03 16:00
X
Press the
buttons to scroll through the groups.
To manually invoke a test on a group of luminaires, highlight the required group and then press the
button to
highlight the "Period" field. Use the
number
keys to enter the required duration and then press the
✔
button to
confirm. The test is immediately started and is shown as "Running" on the display.
[LIGHTING TEST GROUPS] More>
Group Period Date Time Result
2
5 mins
06/01/04 14:26 Running
3 30 mins 02/10/03 08:30
✔
4 5 mins 03/11/03 16:00
✔
5
When the test is completed, the result is shown. To view further information, press the
button. The display
shows details of the number of luminaires tested, the number of luminaires that failed test and the type of test
(automatic / manual) along with the automatic test number if appropriate.
[LIGHTING TEST GROUPS] <More
Group Qty-lights Fails Auto/manual
1
24
0 Auto-001
2 30 0 Manual
3 25 0 Auto-002
4 14 3 Auto-003
To view the individual luminaire test results, scroll
to the appropriate group and press the
✔
button to view
all luminaires (passes and failures) or, press the
button to highlight the fails number and then press the
✔
button to view just the failures. The display then shows a list of the devices tested as follows:
[TEST GROUP 4] More>
Lp:Adrs Result
1:011 x Main Supply Off
1:012
✔
1:026 x Low Light Output ( 1)
1:045 x Battery = 1.4V Low
The display shows the address of the device (Loop Number and Loop Address) and a description of the failure
detected.