3.2.6.5 View - Panel
The View Panel Option provides a diagnostic readout of the operational condition and readings for the internal
panel electronic circuits. When the option is selected, the display shows a list of the circuits. For example:
[Panel Circuits]
ITEM DESCRIPTION VALUE STATE
03.0 Battery 27.4V Normal
04.0 Charger 27.6V Normal
05.0 Earth Monitor 1.5V Normal
06.0 Aux Supply 0mA Normal
The following table lists the internal panel circuits and indicates the values that can be displayed.
Item
Description
Value Range
Normal
Possible States
03.0
Battery
0V
– 30V
27.6V
Normal
Too High, Too Low
04.0
Charger
0V
– 30V
28.0V
Normal
Too High, Too Low
05.0
Earth Monitor
0V
– 30V
1.3V
Normal
Too High, Too Low
06.0
Aux Supply
0mA
– 300mA
2
Normal
Too High
07.0
1
st
Loop Load
3
0mA
– 500mA
Normal
Open Circuit, Too High, Short
Circuit
08.0
1
st
Loop V.Out
24V
– 32V
Normal
09.0
1
st
24V
– 32V
Normal
10.0
Panel Switch Inputs
L/H
L
Normal
Programmable inputs
to
Normal
10.7
L/H
L
Normal
11.0
Relay 1
–
–
Normal
11.1
Relay 2
–
–
Normal
11.2
Output 1
–
–
Normal
to
11.9
Output 8
–
–
Normal
13.0
Control Panel
–
–
14.0
Main Supply
–
–
Normal
Press the
buttons to scroll through the panel internal circuits. Press the
‘Esc’
button
to return to the main
view menu.
2
Depends on the panel configuration, installation and current operating condition.
3
Loop Load, V.Out and V.In displayed for each loop driver. If the Signalling circuits are wired as Radial Type circuits, then the Loop Input
Voltages (V.IN) are not applicable.