SECTION 20
Data Field Descriptions
The following is a description of all data fields provided by this control. Make
entries as described for each field.
*00
INSTALLER CODE
| | |
0001-9999 = 4-digit installer's code
The Installer's Code is reserved for installation company use, and is the
only code that can be used to enter Programme mode from the keypad.
This code cannot be used to disarm the system if it was not used to arm
the system. This code cannot reenter programming mode if exited by the
*98 command.
*01
INSTALLER CODE RESTRICTION
[0]
1= Yes,Master Code keying opens a 15 second time window in which the
Installer Code can be used (Norwegian requirement)
0= No, normal usage of Installer Code during disarmed period
*03
FINAL CONTACT SET (partition-specific)
[0]
1= Yes, the exit delay will be infinitely long and the system will arm 5
seconds after the Zone Type 01 exit door opens and closes or closes if
already open and that condition was allowed prior to arming
0= No
*04
AUTOBYPASS EXIT ROUTE FAULTS (partition-specific)
[0]
1= Yes, autobypass of unsealed burglary zones after a 2nd attempt to
arm within 15 seconds after arming is rejected and the open zones
are displayed (Swedish requirement)
0= No
*05
ARM WITH LOW BATTERY
[0]
1= Yes, allowing the user to override a system low battery condition and
arm the system or a partition
0= No, arming is prohibited when a low system battery is present
(ANPI requirement)
*06
ZONE TYPE 5 ALWAYS ALARM
[0]
1 = fault of a type 5 (tamper) zone shall cause a full alarm in any
arming mode (disarmed or armed)
0 = fault in a type 5 zone shall cause a trouble in the disarmed state and
a full alarm in any armed mode
*07
ALLOW ARMING WITH FAULTS IN EXIT ROUTE
[0]
1 = arming can proceed with zone faults present in any of the exit route
zones (zone types 1, 2, 4 and 10), wherein a fault remaining in any of
these zone types at the end of exit delay (for AWAY/MAXIMUM
arming and in zone types 1 and 2 for STAY/INSTANT arming) will
result in a burglary alarm. Automatic bypass of the faulted zones is
achieved (instead of alarm) if field 1*20 is also enabled.
0 = all zones must be intact in order for arming to take place
*08
SELF ACTIVATING SIREN OUTPUT
[0]
1= Yes, alarm output is normally activated and turns off during alarms
(ANPI requirement)
0= No, alarm output is normally off and activates during an audible
alarm