Time-Driven Events
These are the schedules used to activate outputs, bypass zones, etc. based on a time
schedule. There are 20 of these events that may be programmed for the system, with
each event governed by the previously defined time windows.
The actions that can be programmed to automatically activate at set times are relay
commands, arm/disarm and zone bypassing commands, and open/close access
conditions.
To fill out the worksheet:
1) First enter the schedule number (01-20) and time window number (01-
20), and note the day of the week the action is desired.
2) Enter the code for the desired action and action specifier. The action
codes are the events that are to take place when the scheduled time is reached.
Each action also requires an action specifier, which defines what the action will
affect (relay, relay group, partition, zone list, user group). The action specifier
varies, depending on the type of action selected.
The following is a list of the "Action" codes (desired actions) used when
programming time driven events. Note that these codes are independent of the
"relay codes" programmed during the #93 Menu Mode–Relay Programming mode.
Relay Commands
Action Code Action Specifier
01 Relay
On
Relay
#
02 Relay Off
Relay #
03 Relay Close for 2 seconds
Relay #
04 Relay Close XX minutes (set in field 1*74)
Relay #
05 Relay Close YY seconds (set in field 1*75)
Relay #
06 Relay Group On
Relay Group #
07 Relay Group Off
Relay Group #
08 Relay Group Close for 2 seconds
Relay Group #
09 Relay Group Close XX minutes (set in field 1*74)
Relay Group #
10 Relay Group Close YY seconds (set in field 1*75)
Relay Group #
Arm/Disarm Commands
Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid choices for
automatic arming and disarming functions.
"During" can be used to arm or disarm the control for specific time only. For example,
if "during" is selected with arm-stay, the system will arm-stay at the beginning of the
window and disarm at the end of the window.
Action Code Action Specifier
20 Arm-Stay
Partition(s)
21 Arm Away
Partition(s)
22 Disarm
Partition(s)
23 Force Arm Stay (Auto-bypass faulted zns)
Partition(s)
24 Force Arm Away (Auto-bypass faulted zns)
Partition(s)
The auto-arm warning (field 2*06) applies.
Bypass Commands
Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid choices for
bypass commands. If 3 (During) is selected for auto-bypassing, the system will
bypass the zone(s) specified on a particular Zone List at the beginning of the window
and unbypass the zone(s) at the end of the window. If it is selected for auto
unbypassing, the system will remove the bypass of the zone(s) at the beginning of the
window and will restore the bypass of the zone(s) at the end of the window.