– 96 –
Zone Alarm Reports
ALARM, ID DIGIT?
1 = YES 0 = NO 0
Press 1 (Y) to enter alarm report codes for zones.
Press 0 (N) to skip to the next main menu option.
ENTER ZONE NO.
000 = QUIT 001
Enter the zone number for which you are entering
the report code. Press
✴
to continue.
001 REPORT CODE
1st 00 2nd 00 00
Enter the first digit of the alarm report code
(double-digit entry) and press
✴
.
Enter the 2nd
digit of the alarm report code. Press
✴
.
ENTER ZONE NO.
000 = QUIT 001
Enter the zone number for which you are entering
the report code. When all zone alarm codes have
been programmed, enter 000 to Quit. Press
✴
.
QUIT REPORT MENU
1 = YES 0 = NO 0
If you have completely finished entering report
codes, press 1 (Y) to quit Report Code
Programming mode. If you wish to enter other
system report codes, enter 0(N) and press
✴
.
Restore/Supervisory Codes
RESTR, SUPV. CODE
1 = YES 0 = NO 0
Press 1 (Y) to enter restore and supervisory codes for zones.
ENTER ZN FOR GRP
000 = QUIT 001
Enter one zone for each group of 16 zones (001-016, 017-032,
etc.)
ALARM RESTORE
GRP 001-016 00
Enter the first digit of the alarm restore report code for this
group of zones (double-digit entry). The second digit will be
the ID (second) digit of the alarm report code for each zone (if
programmed). Press
✴
to continue.
TROUBLE
GRP 001-016 00
Enter the first digit of the trouble report code for this group
of zones (double-digit entry). The second digit will be the ID
(second) digit of the alarm report code for each zone (if
programmed). Press
✴
to continue.
TROUBLE RESTORE
GRP 001-016 00
Enter the first digit of the trouble restore code (single-digit
entry) and press
✴
.
The second digit will be the ID (second)
digit of the alarm report code for each zone (if programmed).
Press
✴
to continue.
BYPASS
GRP 001-016 00
Enter the first digit of the bypass report code (double-digit
entry) and press
✴
.
The second digit will be the ID (second)
digit of the alarm report code for each zone (if programmed).
Press
✴
to continue.
BYPASS RESTORE
GRP 001-016 00
Enter the first digit of the bypass restore report code (double-
digit entry) and press
✴
.
The second digit will be the ID
(second) digit of the alarm report code for each zone (if
programmed). Press
✴
to continue.
ENTER ZN FOR GRP
000 = QUIT 017
Enter one zone for each group of 16 zones. When finished
entering restore and supervisory codes for all zone groups,
enter 000 and press
✴
to continue.
QUIT REPORT MENU
1 = YES 0 = NO 0
If you have completely finished entering report codes, press 1
(Y) to quit Report Code Programming mode. If you wish to
enter other system report codes, enter 0 (N) and press
✴
to
continue.