SECTION 13
TESTING FOR SPILLAGE
Close all doors and windows to the room containing the appliance.
Let the fire run on HIGH for five minutes.
Take a smoke match, light it, and using a smoke match tube, hold it at the top edge of
the fire opening, 25mm down and 25mm in.
Run the smoke match across the opening, all the smoke should be drawn away up the
flue.
Any smoke returning into the room indicates that spillage is occurring.
If the initial spillage test fails, run the fire for a further 10 minutes and repeat the test.
Please Note: If using the Super Convector firebox and the spillage test fails please
remove the spigot restrictor making sure to replace the screws back in to their positions
and re-test.
When the test has been completed sucessfully, repeat with any extractor fans in the
premises running on the highest setting, with the room doors open.
Finally, repeat with all doors open.
DO NOT allow the fire to be used until the test has sucessfully passed.