5. Setting up the device
17
Assignment (deposit) of key functions,
tASt:
Default:
no
For the operation mode, special functions can be deposited on the navigation keys
[
▲
] [
▼
]
, in
particular this function is made for devices in housing size 48x24mm which do not have a 4th
key (
[O]
-key). If the min/max-memory was activated by
EHtr
, all measured min/max-values are
saved during operation and can be recalled via the navigation keys. The values get lost by
restart of the device. If the threshold value correction
LI.12
or
LI.34
is choosen, the values of the
threshold can be changed during operation without disturbing the operating procedure. With
tArA
the device is tared to zero and saved permanently as offset. The device confirms the
correct taring by showing
ooooo
in the display.
Set.tA
switches into the offset value and can be
changed via the navigation keys
[
▲
] [
▼
]
. Via
totAL
the current value of the totaliser can be
displayed, after this the device changes back on the parameterised display value. If
tot.rE
was
deposited, the totaliser can be set back by pressing of the navigation keys
[
▲
] [
▼
]
, the device
acknowledges this with
ooooo
in the display. The configuration of
EHt.rE
deletes the min/max-
memory. Under
ActuA
the measurand is shown, after this the display returns to the parameter-
ised display value. If
AbS.UA
(absolute value) was selected, the display shows the value that has
been measured since voltage connection, without consideration of a previous taring. Via
selection
L1.1
,
L1.1-2
,
li.1-3
,
l1.1-4
, in case of 8 switching points
li.1-5
…
li.1-8
, threshold values can be
addressed via the navigation keys; they can be changed digit per digit or taken over by pushing
the
[P]
-key. The adjustment is taken over directly, an excisting limit value monitoring and the
current measurement will not be influenced by this. If
no
is selected, the navigation keys are
without any function in the operation mode.
Display flashing,
FLASH:
Default:
no
A display flashing can be added as additional alarm function either to single or to a combination
of off-limit condition. With
no
, no flashing is allocated.
Parameterisation level
Menu level