7. Alarms / Relays
This device has 8 virtual alarms that can monitor one limit value in regard of an undercut or exceedance.
Each alarm can be allocated to an optional relay output S1-S4; furthermore alarms can be controlled by
events like e.g. Hold or min/max-value.
7. Alarms / Relays
Function principle of alarms / relays
Operating current / quiescent current
Working principle
Broadness of the window between the switching thresholds
Hysteresis
Threshold / limit value of the change-over
Switching threshold
Deactivated, instantaneous value, min/max-value, hold-value, totaliser
value, sliding average value, constant value, difference between
instantaneous value and constant value or an activation via the digital
input
Alarm / Relay x
Operating current
By operating current the alarm S1-S2 is
off
below the threshold and
on
on reaching the
threshold.
Quiescent current
By quiescent current the alarm S1-S2 is
on
below the threshold and switched
off
on
reaching the threshold.
Switching-on delay
The switching-on delay is activated via an
alarm and e.g. switched 10 seconds after
reaching the switching threshold, a short-term
exceedance of the switching value does not
cause an alarm, respectively does not cause a
switching operation of the relay. The
switching-off delay operates in the same way,
keeps the alarm / the relay switched longer for
the parameterised time.